Inspections for the day of: Wednesday, September 25, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-01427 FIRE-Conference9/25/20199/25/20199/25/2019 3:47:51 PMPDONE
Fire conference complete.

call to meet // Jon Phone #: ###-####
FIR19-00331 INSP-Sprinkler Rough-in9/25/20199/25/20199/25/2019 3:47:06 PMPCANC
Duplicate inspection request, this request is cancelled.

Randy Phone #: ###-####
FIR19-00331 INSP-Sprinkler Rough-in9/25/20199/25/20199/25/2019 3:46:19 PMPPASS
Rough to cover inspection for remaining overhead fire sprinkler piping in area of work complete, approved for cover.

Randy Phone #: ###-####
BLD19-03648 FIRE-Final Inspection9/25/20199/25/20199/25/2019 3:12:00 PMPFAIL
Provide fire extinguisher as stated on city approved drawings. Provide sprinkler escutcheon in restroom, escutcheon is missing. Remove thumb-turn deadbolt on rear exit door, door hardware must comply with the 2015 Intenational fire code, section 1010.1.9.1.

ins Scott Phone #: ###-####
FIR19-00583 INSP-Sprinkler Rough-in9/24/20199/25/20199/25/2019 11:35:08 AMAPASS
Previously noted items have been corrected, rough to cover inspection is complete, approved for cover.

Contact Noemi Carerro 208###-#### 30 min prior to RTC insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00702 INSP-Sprinkler Rough-in/Hydro9/24/20199/25/20199/25/2019 11:34:32 AMADONE
Hydrostatic test for underground supply witnessed, no pressure loss observed.

Underground rough ; hydro - call James before heading out! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00702 INSP-Sprinkler Rough-in9/25/20199/25/20199/25/2019 11:33:51 AMAPASS
Rough to cover inspection for underground supply complete, approved for cover.

FIR19-00682 INSP-Sprinkler Rough-in9/23/20199/25/20199/25/2019 10:35:59 AMAFAIL
2 pendant heads are less than 4 inches from wall, a minimum of 4 inches is required per NFPA 13. All insulation needs to be in place and secured, insulation is blocking some of the upright heads.

Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00672 INSP-Sprinkler Rough-in9/25/20199/25/20199/25/2019 10:18:27 AMPPASS
Plan mods have been accepted, all tenting is in place, cover is approved for overhead fire sprinkler piping.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00540 INSP-Sprinkler Rough-in9/24/20199/25/20199/25/2019 10:13:36 AMAPART
Tenting inspection for units 1 and 2, starting from the southside complete, approved for cover, Remaining living units to be inspected at a later date.

Robert Chambers is the contact. This rough-in is for the 3rd floor. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00562 INSP-Sprinkler Rough-in9/24/20199/25/20199/25/2019 10:11:53 AMAPASS
Rough to cover inspection for overhead fire sprinkler pipng above hardlids complete, hardlids approved for cover.

TOM Phone #: ###-####
FIR19-00590 INSP-Final Inspection9/24/20199/25/20199/24/2019 2:56:54 PMAPASS
Final fire alarm inspection for area of work complete.