BLD18-01890
| FIRE-Final Inspection | 9/26/2019 | 9/27/2019 | 9/27/2019 1:16:52 PM | P | FAIL |
|
|
Provide fire sprinkler in area as discussed outside of phone room. Items are stored closer than 18 inches to ceiling, per NFPA13, section 8.5.6, a minimum of 18 inches of clearance is required from bottom of deflector to top storage.
Bill Phone #: ###-####
|
FIR19-00670
| INSP-Sprinkler Rough-in | 9/26/2019 | 9/27/2019 | 9/27/2019 11:46:20 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Adam Phone #: ###-####
|
FIR19-00516
| INSP-Sprinkler Rough-in | 9/26/2019 | 9/27/2019 | 9/27/2019 11:43:38 AM | A | PASS |
|
|
Rough to cover inspection for undergound supply and remote FDC piping complete, approved for cover.
Jeff Chaney is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00584
| INSP-Final Inspection | 9/26/2019 | 9/27/2019 | 9/27/2019 9:40:26 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-04631
| FIRE-Final Inspection | 9/26/2019 | 9/27/2019 | 9/27/2019 9:22:58 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, heat trace inspection has been completed, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signatures have been provided on final sign off card for associated trades.
call rob 2089990578 Phone #: ###-#### Inspection requested via web by J.C. Murray
|
FIR18-00360
| INSP-Final Inspection | 9/27/2019 | 9/27/2019 | 9/27/2019 9:20:53 AM | A | PASS |
|
|
Plan mods have been approved and verified, final fire alarm inspection is complete
|
FIR18-00360
| INSP-Sprinkler Rough-in/Hydro | 9/27/2019 | 9/27/2019 | 9/27/2019 9:20:38 AM | P | CANC |
|
|
Wrong inspection type for inspection request, this request is cancelled.
.
David Phone #: ###-####
|
FIR18-00608
| INSP-Final Inspection | 9/27/2019 | 9/27/2019 | 9/27/2019 8:15:07 AM | A | PASS |
|
|
Final inspection was completed on 17SEPT2019
|
FIR18-00845
| INSP-Final Inspection | 9/27/2019 | 9/27/2019 | 9/27/2019 8:14:35 AM | A | PASS |
|
|
Final inspection was completed on 17SEPT2019.
|
BLD17-02261
| FIRE-Final Inspection | 9/26/2019 | 9/27/2019 | 9/27/2019 12:00:00 AM | A | CANC |
|
|
David Phone #: ###-#### cancel per david, wrong permit
|
BLD17-02262
| FIRE-Final Inspection | 9/26/2019 | 9/27/2019 | 9/27/2019 12:00:00 AM | A | CANC |
|
|
David Phone #: ###-#### cancel per david wrong permit
|