Inspections for the day of: Friday, September 27, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-01890 FIRE-Final Inspection9/26/20199/27/20199/27/2019 1:16:52 PMPFAIL
Provide fire sprinkler in area as discussed outside of phone room. Items are stored closer than 18 inches to ceiling, per NFPA13, section 8.5.6, a minimum of 18 inches of clearance is required from bottom of deflector to top storage.

Bill Phone #: ###-####
FIR19-00670 INSP-Sprinkler Rough-in9/26/20199/27/20199/27/2019 11:46:20 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Adam Phone #: ###-####
FIR19-00516 INSP-Sprinkler Rough-in9/26/20199/27/20199/27/2019 11:43:38 AMAPASS
Rough to cover inspection for undergound supply and remote FDC piping complete, approved for cover.

Jeff Chaney is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00584 INSP-Final Inspection9/26/20199/27/20199/27/2019 9:40:26 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-04631 FIRE-Final Inspection9/26/20199/27/20199/27/2019 9:22:58 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, heat trace inspection has been completed, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signatures have been provided on final sign off card for associated trades.

call rob 2089990578 Phone #: ###-#### Inspection requested via web by J.C. Murray
FIR18-00360 INSP-Final Inspection9/27/20199/27/20199/27/2019 9:20:53 AMAPASS
Plan mods have been approved and verified, final fire alarm inspection is complete
FIR18-00360 INSP-Sprinkler Rough-in/Hydro9/27/20199/27/20199/27/2019 9:20:38 AMPCANC
Wrong inspection type for inspection request, this request is cancelled.

.

David Phone #: ###-####
FIR18-00608 INSP-Final Inspection9/27/20199/27/20199/27/2019 8:15:07 AMAPASS
Final inspection was completed on 17SEPT2019
FIR18-00845 INSP-Final Inspection9/27/20199/27/20199/27/2019 8:14:35 AMAPASS
Final inspection was completed on 17SEPT2019.
BLD17-02261 FIRE-Final Inspection9/26/20199/27/20199/27/2019 12:00:00 AMACANC
David Phone #: ###-#### cancel per david, wrong permit
BLD17-02262 FIRE-Final Inspection9/26/20199/27/20199/27/2019 12:00:00 AMACANC
David Phone #: ###-#### cancel per david wrong permit