FIR19-00572
| INSP-Final Inspection | 9/3/2019 | 9/3/2019 | 9/3/2019 3:08:39 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|
FIR19-00487
| INSP-Final Inspection | 9/3/2019 | 9/3/2019 | 9/3/2019 3:08:05 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
BLD19-03336
| FIRE-Final Inspection | 9/3/2019 | 9/3/2019 | 9/3/2019 12:47:30 PM | P | FAIL |
|
|
Service all exit signs (total of 4) as discussed, all exit lights did not operate with test button, lost internal illumination when disconnected from AC power.
Call 30 minute ahead (in Meridian) // Melissa Phone #: ###-####
|
FIR19-00255
| INSP-Final Inspection | 9/3/2019 | 9/3/2019 | 9/3/2019 12:28:13 PM | P | CANC |
|
|
Inspection request cancelled per conversation with point of contact due to ground fault issue, inspection will be rescheduled after repair i made.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00487
| INSP-Sprinkler Rough-in | 9/3/2019 | 9/3/2019 | 9/3/2019 11:18:37 AM | P | CANC |
|
|
Inspection request was a final, this request is cancelled.
Mike Phone #: ###-####
|
BLD19-03262
| FIRE-Final Inspection | 8/30/2019 | 9/3/2019 | 9/3/2019 10:01:19 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, card has been signed.
Brandi Phone #: ###-####
|
FIR19-00523
| INSP-Final Inspection | 8/30/2019 | 9/3/2019 | 9/3/2019 9:42:54 AM | A | FAIL |
|
|
Relocate manual pull station to a code compliant location, cuurent location is less than 9 foot from corner edge of hood.
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
|
FIR19-00543
| INSP-Final Inspection | 8/30/2019 | 9/3/2019 | 9/3/2019 8:40:30 AM | A | FAIL |
|
|
As discussed with Kristen, battery fault was suppose to repaired with last tenant, battery fault was not repaired, as of this entry battery fault was still on panel, Kristen was informed that if fault was still on panel then inspection request would be a fail.
Damien Phone #: ###-####
|