Inspections for the day of: Tuesday, September 3, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00572 INSP-Final Inspection9/3/20199/3/20199/3/2019 3:08:39 PMPPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Jonathan LaFond
FIR19-00487 INSP-Final Inspection9/3/20199/3/20199/3/2019 3:08:05 PMPPASS
Final fire sprinkler inspection for area of work complete.
BLD19-03336 FIRE-Final Inspection9/3/20199/3/20199/3/2019 12:47:30 PMPFAIL
Service all exit signs (total of 4) as discussed, all exit lights did not operate with test button, lost internal illumination when disconnected from AC power.

Call 30 minute ahead (in Meridian) // Melissa Phone #: ###-####
FIR19-00255 INSP-Final Inspection9/3/20199/3/20199/3/2019 12:28:13 PMPCANC
Inspection request cancelled per conversation with point of contact due to ground fault issue, inspection will be rescheduled after repair i made.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00487 INSP-Sprinkler Rough-in9/3/20199/3/20199/3/2019 11:18:37 AMPCANC
Inspection request was a final, this request is cancelled.

Mike Phone #: ###-####
BLD19-03262 FIRE-Final Inspection8/30/20199/3/20199/3/2019 10:01:19 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, card has been signed.

Brandi Phone #: ###-####
FIR19-00523 INSP-Final Inspection8/30/20199/3/20199/3/2019 9:42:54 AMAFAIL
Relocate manual pull station to a code compliant location, cuurent location is less than 9 foot from corner edge of hood.

Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson
FIR19-00543 INSP-Final Inspection8/30/20199/3/20199/3/2019 8:40:30 AMAFAIL
As discussed with Kristen, battery fault was suppose to repaired with last tenant, battery fault was not repaired, as of this entry battery fault was still on panel, Kristen was informed that if fault was still on panel then inspection request would be a fail.

Damien Phone #: ###-####