Inspections for the day of: Monday, September 30, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00563 FIRE-Final Inspection9/30/20199/30/20199/30/2019 3:15:13 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signature provide on sign off card.

call for access- brandon Phone #: ###-####
FIR19-00269 INSP-Final Inspection9/30/20199/30/20199/30/2019 3:06:36 PMPFAIL
Provide head box with head wrench and correct number of spare heads. Circuit breaker for flow switch tripped with flow switch activation, could not get bell to operate, bell operation will need to be repaired.

Adam Phone #: ###-####
FIR19-00091 INSP-Final Inspection9/30/20199/30/20199/30/2019 3:02:54 PMPPASS
Final inspection for underground supply complete.

Adam Phone #: ###-####
FIR19-00066 INSP-Conference9/27/20199/30/20199/30/2019 11:34:48 AMAPART
Fire conference partially complete, walked level 1 and basement level, technician on site has a few minor corrections, will verify corrections on final walk through, still need to perform walk through on level 2.

hone #: ###-#### Inspection requested via web by Ken Webster
FIR19-00746 INSP-Final Inspection9/30/20199/30/20199/30/2019 9:16:04 AMPCANC
Hood suppression system is not integrated with the fire alarm system as of this entry, hood suppression system must be tied into fire alarm system before final acceptance inspection, per conversation with point of contact, this request is cancelled and will be rescheduled when fire alarm integration is complete.

Robert is the contact. Phone #: ###-#### Inspection requested via web by Scott Corriea
FIR19-00676 INSP-Final Inspection9/27/20199/30/20199/30/2019 9:14:10 AMAPASS
Final fire sprinkler inspection for area of work complete.
FIR19-00676 INSP-Sprinkler Rough-in9/27/20199/30/20199/30/2019 9:13:45 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Adien Phone #: ###-####
FIR19-00682 INSP-Sprinkler Rough-in9/27/20199/30/20199/30/2019 8:43:52 AMACANC
Point of contact cancelled inspection due to insulation not in place in areas where it was removed, insulation needs to be in place for sprinkler spacing.

Call James when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00634 INSP-Final Inspection9/27/20199/30/20199/30/2019 8:03:03 AMACANC
Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
BLD19-01427 FIRE-Final Inspection9/27/20199/30/20199/30/2019 7:50:15 AMAPART
Areas inspected are for phase 1 TCO, fire sprinkler ispection for phase 1 TCO complete, fire alarm inspection for phase 1 TCO complete, fire extinguishers are placed with current inspection tags for TCO phase 1, final inspection for life fire safety phase 1 TCO complete, ceilings tiles are to be placed in little corridor north of the elevators, ceilings tiles need to be in place for fire sprinkler heat collection, to be placed before final BLD inspection for phase 1 TCO.

Jon Phone #: ###-####
FIR19-00671 INSP-Alarm Testing9/27/20199/30/20199/30/2019 7:46:46 AMAPART
Fire alarm inspection/testing for phase 1 TCO complete.

As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price