Inspections for the day of: Tuesday, September 4, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00320 INSP-Final Inspection8/31/20189/4/20189/4/2018 2:53:33 PMPPASS
Final commercial hood fire suppression system inspection complete.

Dave Phone #: ###-####
FIR18-00666 INSP-Final Inspection8/31/20189/4/20189/4/2018 2:53:33 PMPPASS
Final commercial hood fire suppression system inspection complete.

Dave Phone #: ###-####
FIR18-00445 INSP-Final Inspection8/29/20189/4/20189/4/2018 2:53:30 PMPPASS
Final fire alarm inspection for area of work complete.

Final inspection for upstairs ansul hood. Joe from Captive Air, Dave with State Fire, Peter with Crane Alarm. Phone #: ###-#### Inspection requested via web by Laura Tyson
FIR18-00639 INSP-Sprinkler Rough-in9/4/20189/4/20189/4/2018 1:47:23 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.

John Phone #: ###-####
FIR18-00610 INSP-Sprinkler Rough-in9/4/20189/4/20189/4/2018 1:46:39 PMPPART
Inspection for beam clamps/retaining straps and eartquake sway bracing attachments inspected on level 1 before fire proofing complete, all installed correctly, points of attachment approved for cover, overhead fire sprinkler piping to be inspected at a later date.

MIke Phone #: ###-####
FIR18-00428 INSP-Sprinkler Rough-in9/4/20189/4/20189/4/2018 10:32:53 AMAPART
Rough in inspection for overhead fire sprinkler piping on level 3 complete, a cover inspection for finish drops/sprinklers will be required before finish ceiling can be installed.
FIR18-00428 INSP-Sprinkler Rough-in/Hydro8/31/20189/4/20189/4/2018 10:31:03 AMPPART
Hydrostatic test for level 3 overehad fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Tony Cetani is the contact for this RTC/Hydro inspection. We appreciate your help with this. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00159 INSP-Sprinkler Rough-in8/31/20189/4/20189/4/2018 10:28:01 AMACANC
Phone #: ###-#### >> Inspection requested via web by Matthew Lewis Inspection cancelled from web by: Randy Knutson
BLD17-04354 FIRE-Final Inspection8/31/20189/4/20189/4/2018 9:47:43 AMAFAIL
Provide fire extinguisher with a current inspection tag as discussed. Provide proprerty address for building on road address side of street as discussed. (Building is a corner lot).

Please call ahead for access - Austin Phone #: ###-####
BLD14-03688 FIRE-Final Inspection8/31/20189/4/20189/4/2018 9:18:55 AMAPASS
Final life fire safety inspection complete.

Victoria Phone #: ###-####
BLD14-02173 FIRE-Final Inspection8/31/20189/4/20189/4/2018 9:18:17 AMAPASS
Final life fire safety inspection complete.

Victoria Phone #: ###-####
FIR18-00239 INSP-Sprinkler Rough-in8/31/20189/4/20189/4/2018 8:17:54 AMPCANC
Todd Ketterling is the contact for this inspection. He is requesting a pump test and hoping for a PM appointment. We really appreciate your help. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus