Inspections for the day of: Friday, September 7, 2018.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF18-00096 INSP-Final9/4/20189/7/20189/7/2018 2:08:57 PMPFAIL
No phone number provided for point of contact. Fire alarm notification required in area of work (any permit is required for any and all fire alarm modifications). Provide emergency lighting for the exterior at the emergency exit discharge landings per IFC section 1008.3.2.

>> Inspection requested via mobile web by Kenny
BLD18-01518 FIRE-Final Inspection9/6/20189/7/20189/7/2018 1:48:33 PMPPART
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are placed with current inspection tags, emergency lighting for exterior discharge landings to be installed as discussed, 30 day TCO authorized contingent on the exterior emergency lighting getting installed, after exterior emergency lighting is installed a follow up life fire safety inspection will need to be completed. Remove thumbturn deadbolts as discussed before next final life fire safety inspection.



Ken Barr Phone #: ###-####
BLD18-01829 FIRE-Final Inspection9/6/20189/7/20189/7/2018 1:13:10 PMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Larren Phone #: ###-####
FIR18-00645 INSP-Final Inspection9/6/20189/7/20189/7/2018 1:13:10 PMAPASS
Final fire sprinkler inspection complete.

Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00638 INSP-Final Inspection9/6/20189/7/20189/7/2018 1:13:09 PMPPASS
Final fire alarm inspection for area of work complete.

please call 1/2 hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
BLD18-02764 FIRE-Final Inspection9/7/20189/7/20189/7/2018 11:35:08 AMPPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
FIR18-00693 INSP-Final Inspection9/7/20189/7/20189/7/2018 11:29:58 AMPPASS
Final fire sprinkler inspection for area of work complete.

ADAM CHITWOOD Phone #: ###-#### Inspection requested via web by Brodie Stenquist
BLD18-02474 FIRE-Final Inspection9/6/20189/7/20189/7/2018 11:10:43 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.

Andrew Phone #: ###-####
BLD17-03244 FIRE-Final Inspection9/7/20189/7/20189/7/2018 10:52:29 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Please call Kelly 30 minutes prior to inspection. Phone #: ###-#### Inspection requested via web by Brian McCoy
FIR18-00327 INSP-Final Inspection9/6/20189/7/20189/7/2018 10:51:38 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-02953 FIRE-Final Inspection9/5/20189/7/20189/7/2018 10:36:47 AMAFAIL
Provide sticker on main entry reading "Door to remain unlocked while occupied". Round type door hardware on main entry needs to be changed to code compliant hardware. Thumbturn deadbolt needs to be removed and a double key type needs to be installed.

Morgan Phone #: ###-####
BLD18-02954 FIRE-Final Inspection9/5/20189/7/20189/7/2018 10:35:21 AMAFAIL
Provide sticker on main entry reading "Door to remain unlocked while occupied". Fire extinguishers need to be inspected and tagged accordingly.

Morgan Phone #: ###-####
FIR18-00575 INSP-Final Inspection9/6/20189/7/20189/7/2018 10:19:40 AMAPASS
Final fire sprinkler inspection for area of work complete.

Permit ; Plans are on Henry''s Desk in Operations. Phone #: ###-#### Inspection requested via web by Connie Danes
FIR18-00635 INSP-Sprinkler Rough-in/Hydro9/6/20189/7/20189/7/2018 9:29:54 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00674 INSP-Sprinkler Rough-in/Hydro9/6/20189/7/20189/7/2018 9:20:23 AMADONE
Hydrostatic test for undergorund supply witnessed, no pressure loss observed at contractor provided gauge.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR18-00413 INSP-Final Inspection9/6/20189/7/20189/7/2018 9:18:57 AMAPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-04596 FIRE-Final Inspection9/7/20189/7/20189/7/2018 9:17:54 AMPPART
Project is being worked in phases, fire sprinklers complete for phase 2 (West side of level 7), fire alarms complete for phase 2, fire extinguisher are placed with current inspection tags, final life fire safety inspection for phase 2 west side complete, west side to be inspected at a later date.

Zack Phone #: ###-####
FIR18-00697 INSP-Sprinkler Rough-in9/6/20189/7/20189/7/2018 7:20:42 AMAPASS
Rough to cover inspection for ubnderground supply complete, approved for cover.

underground // Cam Phone #: ###-####
FIR18-00688 INSP-Sprinkler Rough-in9/6/20189/7/20189/7/2018 7:02:16 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

TERRY NELSON Phone #: ###-#### Inspection requested via web by Brodie Stenquist