Inspections for the day of: Monday, September 9, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00633 INSP-Final Inspection9/6/20199/9/20199/9/2019 12:08:15 PMAFAIL
Could not test fire alarm associated items with risers due to floor adhesive in stairwell tower, could not access risers.

Kenny Caldwell is the contact for this final inspection. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00360 INSP-Final Inspection9/6/20199/9/20199/9/2019 12:07:13 PMAFAIL
Audio intelligibility not met in numerous areas. Smoke detector in ADA room on level 1 overspaced, detector is more than 21 foot from corner of room. A/V device in level 1 elevator lobby is overspaced. Notated city approved draiwngs other areas requiring correction. Inspection was stopped on level 2 due to deficiencies noted, all fire sprinkler and initiating devices still and audio visual coverage still need inspected. Monitoring account has been verified, have not checked signals with monitoring as of this entry.

David Phone #: ###-####
BLD19-00278 FIRE-Conference9/6/20199/9/20199/9/2019 10:12:50 AMADONE
Fire conference complete, discussed smoke detector locations for door mag release.

Question about smoke detector location at fire door east of kitchen area. Phone #: ###-#### Inspection requested via web by Corey Hockersmith
FIR19-00540 INSP-Conference9/9/20199/9/20199/9/2019 9:57:26 AMADONE
Letter of compatability needs to be submitted to the fire sprinkler plan reviewer in regards to the foam type insulation coming in contact with the CPVC sprinkler piping. Cover has not been approved for overhead fire sprinkler piping, any cover material installed that blocks the visual inspection for rough in will be required to be removed, as of this entry no cover is approved, fire conference is complete.
BLD18-03122 FIRE-Final Inspection9/6/20199/9/20199/9/2019 8:44:41 AMAFAIL
As noted in Troy Cobbleys entry on the 29AUG2019 inspection request, tenting inspection for fire sprinklers needs to be requested under the associated FIR permit, not the BLD permit.

tinting.... last six // Pat Phone #: ###-####
FIR19-00540 INSP-Sprinkler Rough-in/Hydro9/6/20199/9/20199/9/2019 8:36:08 AMACANC
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus