FIR18-00633
| INSP-Final Inspection | 9/6/2019 | 9/9/2019 | 9/9/2019 12:08:15 PM | A | FAIL |
|
|
Could not test fire alarm associated items with risers due to floor adhesive in stairwell tower, could not access risers.
Kenny Caldwell is the contact for this final inspection. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00360
| INSP-Final Inspection | 9/6/2019 | 9/9/2019 | 9/9/2019 12:07:13 PM | A | FAIL |
|
|
Audio intelligibility not met in numerous areas. Smoke detector in ADA room on level 1 overspaced, detector is more than 21 foot from corner of room. A/V device in level 1 elevator lobby is overspaced. Notated city approved draiwngs other areas requiring correction. Inspection was stopped on level 2 due to deficiencies noted, all fire sprinkler and initiating devices still and audio visual coverage still need inspected. Monitoring account has been verified, have not checked signals with monitoring as of this entry.
David Phone #: ###-####
|
BLD19-00278
| FIRE-Conference | 9/6/2019 | 9/9/2019 | 9/9/2019 10:12:50 AM | A | DONE |
|
|
Fire conference complete, discussed smoke detector locations for door mag release.
Question about smoke detector location at fire door east of kitchen area. Phone #: ###-#### Inspection requested via web by Corey Hockersmith
|
FIR19-00540
| INSP-Conference | 9/9/2019 | 9/9/2019 | 9/9/2019 9:57:26 AM | A | DONE |
|
|
Letter of compatability needs to be submitted to the fire sprinkler plan reviewer in regards to the foam type insulation coming in contact with the CPVC sprinkler piping. Cover has not been approved for overhead fire sprinkler piping, any cover material installed that blocks the visual inspection for rough in will be required to be removed, as of this entry no cover is approved, fire conference is complete.
|
BLD18-03122
| FIRE-Final Inspection | 9/6/2019 | 9/9/2019 | 9/9/2019 8:44:41 AM | A | FAIL |
|
|
As noted in Troy Cobbleys entry on the 29AUG2019 inspection request, tenting inspection for fire sprinklers needs to be requested under the associated FIR permit, not the BLD permit.
tinting.... last six // Pat Phone #: ###-####
|
FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 9/6/2019 | 9/9/2019 | 9/9/2019 8:36:08 AM | A | CANC |
|
|
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|