Inspections for the day of: Monday, October 1, 2018.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-04142 Final9/28/201810/1/201810/1/2018 4:07:43 PMPPASS
PLEASE CALL (APPRENTICE) JAMIE @ # LISTED BEFORE LEAVING FOR FINAL INSPECTION ON 4-5 TON ROOFTOP PACKAGE UNIT. Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
-RTU final ok
MEC18-04425 Pressure Test10/1/201810/1/201810/1/2018 3:12:18 PMPNR
please call Owen 30-40 mins when out so he can meet you onsite to perform test needed for you to witness. Phone #: ###-#### Inspection requested via web by Rick Montgomery- pressure differentional at smoke detector fail - talking with Owen they are going to try mounting the smoke detectors on the outside of the duct and apply the proper sampling tube and retest pressure- manufactures spec states a pressure differential of at least .01 - 1.2
MEC18-03786 Final10/1/201810/1/201810/1/2018 3:03:12 PMPFAIL
Please callMr Lee Walton on your way . He is the owner to be ready to open the door. Phone #: ###-#### Inspection requested via web by Baldomero Guzman- line set penetration needs sealed- A/C fuses need to be 30amp
MEC18-03850 Final10/1/201810/1/201810/1/2018 2:20:37 PMPPASS
final - call cyrus
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
MEC18-04578 Final9/27/201810/1/201810/1/2018 2:18:50 PMPPASS
Please call the Owner, Linda at ###-#### with a 30 minute heads up arrival time. Thanks so much. Phone #: ###-#### Inspection requested via web by David or K Cole- furnace ac coil co ok
MEC18-04598 Rough-in9/28/201810/1/201810/1/2018 1:18:18 PMPNR
Phone #: ###-#### Inspection requested via web by Gary Reeves- crawl not ready- water heater flue needs 3" clearances on horizantal pipe- arma flex rips in attic and walls need fixed
MEC18-04598 Pressure Test9/28/201810/1/201810/1/2018 1:14:17 PMPNR
Phone #: ###-#### Inspection requested via web by Gary Reeves
MIS18-00387 MEC-Conference10/1/201810/1/201810/1/2018 1:13:18 PMPDONE
all work being done w/o permits
- no access to home left notice on front door- any HVAC work being done needs a permit pulled
MEC18-04642 Final10/1/201810/1/201810/1/2018 12:46:11 PMPFAIL
Would like Early PM and call on way. Thank you! Phone #: ###-#### Inspection requested via web by Xanti Berria- water heater flue needs 1" clearances to combustibles in one location in the attic
MEC18-04663 Rough-in9/28/201810/1/201810/1/2018 11:11:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace R/I ok
MEC18-04637 Final9/26/201810/1/201810/1/2018 10:26:22 AMAPASS
Please call Bridget the homeowner when 30 mins in route Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace ac coil co ok
MEC17-05457 Final9/28/201810/1/201810/1/2018 10:08:06 AMAPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- partial final on phase 2- temp occ card signed
MEC18-03811 Rough-in9/28/201810/1/201810/1/2018 9:47:46 AMAPASS
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves
- R/I ok
MEC17-00806 Mec-Aging Inspection10/1/201810/1/201810/1/2018 9:30:54 AM CANC
MEC18-04697 Final9/27/201810/1/201810/1/2018 9:30:02 AMAFAIL
Please call Dave at ###-#### with a 30 minute heads up arrival time. Thank you! Phone #: ###-#### Inspection requested via web by David or K Cole- need to see arma flex finisjhed at the indoor coil- there is also a rip in the arma flex thats needs fixed
MEC17-02006 Mec-Aging Inspection10/1/201810/1/201810/1/2018 9:06:56 AM CANC
MEC17-01544 Rough-in9/28/201810/1/201810/1/2018 9:02:11 AMAPART
Doyle is the contact at the facility. We are inspecting 11 bath vents. He will show to those rooms. Phone #: ###-#### Inspection requested via web by Brian Preece- exhaust fan R/I on rooms 41,59,58,57,45,55,54,53,47,52,50 ok for ceiling cover around exhaust fans- PTAC units will be installed next in 14 rooms total