Inspections for the day of: Thursday, October 24, 2019.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04818 Final10/24/201910/24/201910/24/2019 1:19:20 PMPPASS
Ryan ###-####
Will meet you on site Phone #: ###-#### Inspection requested via web by John Bertram
- final ok
MEC19-04818 Rough-in10/24/201910/24/201910/24/2019 1:19:06 PMPPASS
Ryan ###-####
Will meet you on site Phone #: ###-#### Inspection requested via web by John Bertram
- dyrer vent and 2 exhaust fans R/I ok
MEC19-04797 Final10/23/201910/24/201910/24/2019 12:59:00 PMPPASS
Please call Dave on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace only co ok
MEC19-04771 Pressure Test10/24/201910/24/201910/24/2019 12:04:45 PMPFAIL
can you call Tom at the number above, should there be any issues?

Nat Phone #: ###-#### Inspection requested via web by Nat Golden
- 20lb gas pressure test ok
- gas line penetration needs protective tape installed. Will tag meter when corrections are made
MEC19-04323 Final10/23/201910/24/201910/24/2019 12:03:17 PMPFAIL
BRECK IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
- all gas line penetrations need sealed
MEC19-04497 Final10/17/201910/24/201910/24/2019 12:00:23 PMPFAIL
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 1:30 . Contact for Right Now is Mary ###-####
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
- 5lb flue pressure test fail
MEC19-03896 DOC - Permit Finaled10/24/201910/24/201910/24/2019 11:28:11 AMPPASS
locking caps on A/C ok
MEC19-04602 Rough-in10/23/201910/24/201910/24/2019 10:55:10 AMAFAIL
Call to meet you Phone #: ###-#### Inspection requested via web by Rene Neumeyer
- gas pressure test fail
- gas shut off valve is positioned where it can't be opened 100% re position valve
MEC19-04602 Pressure Test10/23/201910/24/201910/24/2019 10:54:18 AMAFAIL
Call to meet you Phone #: ###-#### Inspection requested via web by Rene Neumeyer
- 20lb gas pressure test fail gauge under 20lb
- make sure gas test is either disconnected from live gas or a double valve open ended tee is installed between new gas line and live gas
MEC19-04808 Pressure Test10/23/201910/24/201910/24/2019 10:28:21 AMAFAIL
MOVED GAS LINE NEED PRESSURE TEST Phone #: ###-#### Inspection requested via web by Andrea Creek
- gas line in shop was under 20lb
- under ground gas line 20lb ok backfill ok
- need to verify gas meter is sized properly for new load
MEC19-04789 Final10/23/201910/24/201910/24/2019 10:07:05 AMAFAIL
Replace existing 4 ton RTU with new 4 ton Rtu with same specs. Phone #: ###-#### Inspection requested via web by jeremy wanders
- need weather tight conduit installed on RTU
MEC19-04780 Rough-in10/23/201910/24/201910/24/2019 9:46:54 AMAFAIL
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
- need stamped Man J onsite
- supply plenum in crawl needs insulated
- cant find fresh air duct due to sheet rock being installed before Mechanical R/I passed
MEC19-04780 Pressure Test10/23/201910/24/201910/24/2019 9:45:35 AMAPASS
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
2- 5lb flue pressure tests ok
- 20lb gas pressure test ok
- tagged meter location
MEC19-04289 Rough-in10/23/201910/24/201910/24/2019 9:15:20 AMAFAIL
Rough In Inspection of Dampers - someone will be on site Phone #: ###-#### Inspection requested via web by Beka Hereau
- duct work ok
- still need proper installation instructions for round fire dampers. All angles need removed to check clearances. remove fire caulk on dampers unless instructions say to do so. Each fire damper will also need an access door installed.
- condensates for units ok
- exhaust side of radiant heaters needs sealed with high temp sealer and need to check clearances on vent throughn roof
MEC18-04255 Mec-Aging Inspection10/24/201910/24/201910/24/2019 8:05:55 AM PASS
Doc Permit Expired ok
MEC18-04255 DOC - Permit Expired10/24/201910/24/201910/24/2019 8:05:41 AMAPASS
Doc Permit Expired ok permit not active
MEC18-05889 Mec-Aging Inspection10/24/201910/24/201910/24/2019 8:05:11 AM PASS
Doc Permit Expired ok
MEC18-05889 DOC - Permit Expired10/24/201910/24/201910/24/2019 8:04:55 AMAPASS
Doc Permit Expired ok permit not active
MEC19-01309 Mec-Aging Inspection10/24/201910/24/201910/24/2019 8:04:18 AM DONE
WIP
MEC19-04420 Rough-in10/23/201910/24/201910/23/2019 4:01:56 PMACANC
Relocated Both vents for water heater and furnace to other part of roof Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
MEC19-04420 Pressure Test10/23/201910/24/201910/23/2019 4:01:54 PMACANC
Relocated Both vents for water heater and furnace to other part of roof Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves