Inspections for the day of: Monday, October 28, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04795 Rough-in10/28/201910/28/201910/28/2019 3:54:06 PMPFAIL
Manual j/d is beside furnace. Thank you Phone #: ###-#### Inspection requested via web by claude croy
- need approved man J onsite
-ductwork needs sealed
- return air is in kitcken and needs relocated
- need to know whos installing fireplace
MEC19-00213 Pressure Test10/28/201910/28/201910/28/2019 3:11:10 PMPPASS
We already passed pressure test out here on 1/23/19. The green tag is missing. Can we get another green tag on site so Intermountain Gas will set their meter. Let me know if we need to do
anything additional. Phone #: ###-#### Inspection requested via web by Angie Maguire
- tagged gas line
MEC19-04846 Final10/28/201910/28/201910/28/2019 2:29:40 PMPCANC
INSTALLER TRAVIS ###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt
MEC19-00342 Final10/28/201910/28/201910/28/2019 2:17:14 PMPFAIL
Final mech, please ring door bell, builder stated she would be there, thanks Phone #: ###-#### Inspection requested via web by Cesar Rodriguez
- A/C needs locking caps installed on service ports
MEC19-00722 Final10/28/201910/28/201910/28/2019 2:16:39 PMPPASS
Final mech, please ring door bell, builder stated she would be there Phone #: ###-#### Inspection requested via web by Cesar Rodriguez
- fireplace final ok
MEC19-04602 Rough-in10/25/201910/28/201910/28/2019 1:38:48 PMPPASS
Call prior to meet us at thejobsite can you let me know if you can make this at around 12:00 let me know Rene Phone #: ###-#### Inspection requested via web by Rene Neumeyer
- R/I ok
- need to check gas piping support in crawl at final
MEC19-04602 Pressure Test10/25/201910/28/201910/28/2019 1:37:54 PMPPASS
Call prior to meet us at thejobsite can you let me know if you can make this at around 12:00 let me know Rene Phone #: ###-#### Inspection requested via web by Rene Neumeyer
- 20lb gas pressure test ok
MEC19-04289 Rough-in10/25/201910/28/201910/28/2019 1:37:04 PMPPART
FIRE Damper Rough In - Inspection Phone #: ###-#### Inspection requested via web by Beka Hereau
- fire damper clearances ok
-all fire caulk needs to be removed and fire damper access doors installed by ceiling R/I
cover
- radiant heater flue clearnaces ok need to caulk all exhaust venting seams
MEC19-04831 Pressure Test10/25/201910/28/201910/28/2019 11:05:34 AMAPASS
Pressure test gas line to shop
please call homeowner when en route if possible ###-#### Renee
Thank you Phone #: ###-#### Inspection requested via web by Nick Drake
- 20lb underground pressure test ok for back fill
MEC19-04636 Final10/24/201910/28/201910/28/2019 9:43:04 AMAFAIL
Call ahead to Regina @ ###-#### Phone #: ###-#### Inspection requested via web by Nicole Smith
- air handler coil ok
- A/C needs locking caps installed on service ports
MIS19-00132 DOC - Permit Finaled10/28/201910/28/201910/28/2019 9:38:15 AMAPASS
Mechanical permits have been issued for work. Doc Permit Final ok
MEC19-04808 Pressure Test10/26/201910/28/201910/28/2019 9:25:16 AMAPART
Thanks, Jeff Creek ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek
- 20lb gas pressure test ok
- contractor stated new CSST from will be ran to furnace. Need to see a pressure test on new piping added into mech room
MEC19-01366 Mec-Aging Inspection10/28/201910/28/201910/28/2019 8:43:47 AM FAIL
Permit has not been active since 4-26-19 when there was no access to home. Schedule inspection with homeowner. Permit will expire at the next mechanical aging inspection if not active.