MEC19-04795
| Rough-in | 10/28/2019 | 10/28/2019 | 10/28/2019 3:54:06 PM | P | FAIL |
|
|
Manual j/d is beside furnace. Thank you Phone #: ###-#### Inspection requested via web by claude croy - need approved man J onsite -ductwork needs sealed - return air is in kitcken and needs relocated - need to know whos installing fireplace
|
MEC19-00213
| Pressure Test | 10/28/2019 | 10/28/2019 | 10/28/2019 3:11:10 PM | P | PASS |
|
|
We already passed pressure test out here on 1/23/19. The green tag is missing. Can we get another green tag on site so Intermountain Gas will set their meter. Let me know if we need to do anything additional. Phone #: ###-#### Inspection requested via web by Angie Maguire - tagged gas line
|
MEC19-04846
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 2:29:40 PM | P | CANC |
|
|
INSTALLER TRAVIS ###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt
|
MEC19-00342
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 2:17:14 PM | P | FAIL |
|
|
Final mech, please ring door bell, builder stated she would be there, thanks Phone #: ###-#### Inspection requested via web by Cesar Rodriguez - A/C needs locking caps installed on service ports
|
MEC19-00722
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 2:16:39 PM | P | PASS |
|
|
Final mech, please ring door bell, builder stated she would be there Phone #: ###-#### Inspection requested via web by Cesar Rodriguez - fireplace final ok
|
MEC19-04602
| Rough-in | 10/25/2019 | 10/28/2019 | 10/28/2019 1:38:48 PM | P | PASS |
|
|
Call prior to meet us at thejobsite can you let me know if you can make this at around 12:00 let me know Rene Phone #: ###-#### Inspection requested via web by Rene Neumeyer - R/I ok - need to check gas piping support in crawl at final
|
MEC19-04602
| Pressure Test | 10/25/2019 | 10/28/2019 | 10/28/2019 1:37:54 PM | P | PASS |
|
|
Call prior to meet us at thejobsite can you let me know if you can make this at around 12:00 let me know Rene Phone #: ###-#### Inspection requested via web by Rene Neumeyer - 20lb gas pressure test ok
|
MEC19-04289
| Rough-in | 10/25/2019 | 10/28/2019 | 10/28/2019 1:37:04 PM | P | PART |
|
|
FIRE Damper Rough In - Inspection Phone #: ###-#### Inspection requested via web by Beka Hereau - fire damper clearances ok -all fire caulk needs to be removed and fire damper access doors installed by ceiling R/I cover - radiant heater flue clearnaces ok need to caulk all exhaust venting seams
|
MEC19-04831
| Pressure Test | 10/25/2019 | 10/28/2019 | 10/28/2019 11:05:34 AM | A | PASS |
|
|
Pressure test gas line to shop please call homeowner when en route if possible ###-#### Renee Thank you Phone #: ###-#### Inspection requested via web by Nick Drake - 20lb underground pressure test ok for back fill
|
MEC19-04636
| Final | 10/24/2019 | 10/28/2019 | 10/28/2019 9:43:04 AM | A | FAIL |
|
|
Call ahead to Regina @ ###-#### Phone #: ###-#### Inspection requested via web by Nicole Smith - air handler coil ok - A/C needs locking caps installed on service ports
|
MIS19-00132
| DOC - Permit Finaled | 10/28/2019 | 10/28/2019 | 10/28/2019 9:38:15 AM | A | PASS |
|
|
Mechanical permits have been issued for work. Doc Permit Final ok
|
MEC19-04808
| Pressure Test | 10/26/2019 | 10/28/2019 | 10/28/2019 9:25:16 AM | A | PART |
|
|
Thanks, Jeff Creek ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek - 20lb gas pressure test ok - contractor stated new CSST from will be ran to furnace. Need to see a pressure test on new piping added into mech room
|
MEC19-01366
| Mec-Aging Inspection | 10/28/2019 | 10/28/2019 | 10/28/2019 8:43:47 AM | | FAIL |
|
|
Permit has not been active since 4-26-19 when there was no access to home. Schedule inspection with homeowner. Permit will expire at the next mechanical aging inspection if not active.
|