MEC19-04453
| Pressure Test | 10/4/2019 | 10/7/2019 | 10/7/2019 3:45:01 PM | P | PASS |
|
|
Kyle-please go as late as possible and please call when on your way Phone #: ###-#### - 20lb gas pressure test ok
|
MEC19-04406
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 3:43:13 PM | P | PASS |
|
|
Please call Wayne Birt about 30 minutes prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - furnace only co ok
|
MEC19-00240
| Pressure Test | 10/7/2019 | 10/7/2019 | 10/7/2019 2:53:49 PM | P | PASS |
|
|
Contact: Robert Church ###-####. Phone #: ###-#### Inspection requested via web by Brent Lacy - 100lb main hydronic 1st and 2nd floor area A/B ok
|
MEC19-03593
| Rough-in | 10/7/2019 | 10/7/2019 | 10/7/2019 2:40:58 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Aaron Alandt - R/I ok
|
MEC19-03593
| Pressure Test | 10/7/2019 | 10/7/2019 | 10/7/2019 2:40:44 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Aaron Alandt - 5lb flue pressure test ok
|
MEC19-04462
| Final | 10/7/2019 | 10/7/2019 | 10/7/2019 1:50:46 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek - furnace flue needs 6" clearances to door frame and line set insulation or ran in b vent with 1" clearances - need to install wet switch on secondary drain
|
MEC19-04351
| Final | 10/7/2019 | 10/7/2019 | 10/7/2019 1:14:54 PM | P | PASS |
|
|
Please call Tech on site (Nolan ###-####) before heading over Phone #: ###-#### Inspection requested via web by Justin Osterhout - furnace only co ok
|
MEC19-04173
| Final | 10/3/2019 | 10/7/2019 | 10/7/2019 12:58:15 PM | P | PASS |
|
|
Call ahead to Johnston @ ###-#### - A/C has been secured to pad and return capped off now. Phone #: ###-#### Inspection requested via web by Nicole Smith - final ok
|
MEC19-04314
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 12:30:52 PM | P | PASS |
|
|
Going in AM to install locking caps. Will send picture when I get it. Phone #: ###-#### Inspection requested via web by Mary LaFayette - final ok
|
MEC19-04390
| Final | 10/2/2019 | 10/7/2019 | 10/7/2019 10:35:10 AM | A | PASS |
|
|
PLEASE CALL BILL THE HOMEOWNER WHEN IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery - furnace only co ok
|
MEC19-03726
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 9:40:59 AM | A | FAIL |
|
|
Mark is not available to answer door from 10-10:30. On a conference call. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - A/C needs locking caps on service ports
|
MEC19-02990
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 9:20:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft - fireplace final ok
|
MEC19-02991
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 9:20:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft - fireplace final ok
|
MEC19-02992
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 9:20:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft - fireplace final ok
|
MEC19-04421
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 8:53:52 AM | A | PASS |
|
|
Bj 208 573 0755 Inspection requested via web by william kerwin - final ok
|
MEC19-04388
| Pressure Test | 10/4/2019 | 10/7/2019 | 10/7/2019 8:53:33 AM | A | PASS |
|
|
Please call Brian 1 / 2 hr. before arrival. - ###-#### Gas pressure test. Phone #: ###-#### Inspection requested via web by Bryan Palmer - 20lb gas pressure test ok - tagged meter location
|
MEC19-03512
| Rough-in | 10/5/2019 | 10/7/2019 | 10/7/2019 8:40:14 AM | A | PASS |
|
|
Stamped Man J will be on site Phone #: ###-#### Inspection requested via web by Michael Stimpson - 5lb and 20lb pressure tests ok - R/I ok - check equipment to man J at final - transfer air for bedrooms at final
|
MEC19-00216
| Final | 10/4/2019 | 10/7/2019 | 10/7/2019 8:29:03 AM | A | PASS |
|
|
Please call when you are headed to the job and I will meet you there and let you in. Phone #: ###-#### Inspection requested via web by Doug Turner - final ok no occ card onsite to sign
|
MEC19-00216
| Card not on site to sign | 10/7/2019 | 10/7/2019 | 10/7/2019 8:28:44 AM | A | PASS |
|
|
Please call when you are headed to the job and I will meet you there and let you in. Phone #: ###-#### Inspection requested via web by Doug Turner - no occ card onsite to sign ok
|
MEC18-03367
| Mec-Aging Inspection | 10/7/2019 | 10/7/2019 | 10/7/2019 8:01:47 AM | | FAIL |
|
|
Electrical permit has still not been issued for ductless split system. Once electrical permit is pulled mechanical permit will be finaled. Permit will expired if not active by next mechanical aging inspection.
|
MEC18-05676
| Mec-Aging Inspection | 10/7/2019 | 10/7/2019 | 10/7/2019 7:58:19 AM | | PASS |
|
|
Doc Permit Expired ok
|
MEC18-05676
| DOC - Permit Expired | 10/7/2019 | 10/7/2019 | 10/7/2019 7:58:01 AM | A | PASS |
|
|
Doc Permit Expired ok permit not active
|