Inspections for the day of: Monday, November 4, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04926 Final11/1/201911/4/201911/4/2019 3:31:52 PMPPASS
installer Jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- final ok
MEC19-04959 Final11/4/201911/4/201911/4/2019 3:16:15 PMPPASS
Please call Rob on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace only co ok
MEC19-04964 Rough-in11/4/201911/4/201911/4/2019 2:01:17 PMPFAIL
Phone #: ###-#### Inspection requested via web by JOSE DUARTE
- man J needs updated with 90% furnace
MEC19-04964 Pressure Test11/4/201911/4/201911/4/2019 1:59:33 PMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE
- 5lb flue pressure test ok
- 20lb gas pressure test ok
- tagged meter location
MEC19-04663 Rough-in10/30/201911/4/201911/4/2019 11:25:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- need stamped Man J onsite
- Access to attic for furnace coil inspection
MEC19-04663 Pressure Test10/30/201911/4/201911/4/2019 11:24:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 20lb gas pressure test ok
- tagged meter location
MEC19-04898 Rough-in11/1/201911/4/201911/4/2019 11:16:41 AMAFAIL
Thank you Phone #: ###-#### Inspection requested via web by Aaron Johns
- Man j needs updated and approved by the City
- fllor boots need sealed to floor
- range vent needs sealed
- If fireplace is staying it needs an inspection and installation instructions onsite
MEC19-01757 Rough-in11/1/201911/4/201911/4/2019 10:52:55 AMAPASS
Ceiling cover. Thank you! Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- ceiling cover R/I ok
MEC19-04898 Pressure Test11/4/201911/4/201911/4/2019 10:26:41 AMAPASS
Thank you Phone #: ###-#### Inspection requested via web by Aaron Johns
- 20lb gas pressure test ok
- tagged meter location
MEC19-04862 Final10/30/201911/4/201911/4/2019 9:34:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-04479 Final11/1/201911/4/201911/4/2019 9:33:49 AMAPASS
Brad Phone #: ###-####
- final ok
MEC18-05981 Mec-Aging Inspection11/4/201911/4/201911/4/2019 8:09:37 AM PASS
Doc Permit Finaled ok
MEC18-05981 DOC - Permit Finaled11/4/201911/4/201911/4/2019 8:09:11 AMAPASS
Doc Permit Final ok