Inspections for the day of: Thursday, February 20, 2020.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00716 Rough-in2/20/20202/20/20202/20/2020 3:51:27 PMPFAIL
call for access- Nathan Phone #: ###-####
- exhaust fan duct connections need sealed
- install nail plates for line set in wall
MEC20-00700 Final2/19/20202/20/20202/20/2020 3:34:23 PMPPASS
Please call Dave when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC20-00714 Final2/20/20202/20/20202/20/2020 2:28:27 PMPPASS
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace only co ok
MEC20-00721 Pressure Test2/20/20202/20/20202/20/2020 2:15:25 PMPPASS
Call Jason with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
- 20lb gas pressure test ok
- 5lb flue pressure test for water heater ok
- tagged meter location
MEC19-03096 Rough-in2/20/20202/20/20202/20/2020 1:36:23 PMPFAIL
Rough-in on men''s and women''s bathroom, final on 2nd, 3rd, and 4th floor if possible. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- plan mod is under review
MEC19-04721 Final2/19/20202/20/20202/20/2020 1:32:19 PMPFAIL
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
- mech closet needs combustion air
MEC20-00646 Rough-in2/19/20202/20/20202/20/2020 11:21:06 AMAFAIL
Homeowner- Bobby Martin ###-#### Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
- A/C needs locking caps installed
- A/C fuses need changed
- pictures will be acceptable
MEC20-00588 Final2/17/20202/20/20202/20/2020 10:25:27 AMAPASS
Homeowner Shane Leslie ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace only co ok
MEC20-00620 Final2/14/20202/20/20202/20/2020 10:04:14 AMAFAIL
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 10 AM. Contact for Right Now is Mary ###-####





Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 5lb flue pressure test fail
- furnace ac coil co ok
MEC19-04184 Final2/19/20202/20/20202/20/2020 9:51:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP
- final ok
MEC20-00699 Final2/19/20202/20/20202/20/2020 9:37:13 AMAPASS
Inspection requested via web by Margie Rowe
- air handler coil HP ok
MEC20-00712 Rough-in2/19/20202/20/20202/20/2020 9:29:43 AMAFAIL
call marco 30 minutes before arriving for home access 208 353 5484 thanks
Phone #: ###-#### Inspection requested via web by marco gomez
- common b vent needs 1" clearances
- all bathrooms need exhaust
- laundry room needs dryer vent and these items need to be added to permit
- will need to see combustion air opening high low for furnace and new location of water heater in basment
- 20lb gas pressure test ok
MEC19-03843 Final2/19/20202/20/20202/20/2020 8:48:42 AMAFAIL
Wes Phone #: ###-####
- A/C needs locking caps
- line set needs UV protection
- gas line penetration needs sealed- need air balance report onsite
MEC20-00507 Final2/19/20202/20/20202/20/2020 8:33:30 AMACANC
Please inspect as early as possible in AM. Annie Cox ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- rescheduled for tomorrow morning with owner
MEC19-03441 Mec-Aging Inspection2/20/20202/20/20202/20/2020 8:14:58 AM FAIL
Permit has not been active since 9-20-19. Schedule inspection with owner when ready. Permit will expire at next mechanical aging inspection if not active.
MEC20-00668 Final2/18/20202/20/20202/18/2020 11:36:16 AMPCANC
Sherry Thomas only home on her lunch hour from 12-1. Hopefully you can make that work. ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette