MEC20-00440
| Rough-in | 2/4/2020 | 2/4/2020 | 2/4/2020 3:58:31 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE - exhaust fans need flex duct hooked up
|
MEC20-00440
| Pressure Test | 2/4/2020 | 2/4/2020 | 2/4/2020 3:57:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by JOSE DUARTE - 5lb flue test fail - 20lb gas pressure test ok - tagged meter location
|
MEC20-00431
| Final | 2/3/2020 | 2/4/2020 | 2/4/2020 2:41:21 PM | P | CANC |
|
|
PLEASE CALL RANDY PRIOR TO ARRIVAL Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - not ready for final
|
MEC20-00431
| Rough-in | 2/4/2020 | 2/4/2020 | 2/4/2020 2:41:00 PM | P | PASS |
|
|
PLEASE CALL RANDY PRIOR TO ARRIVAL Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - R/I and clearances ok - need to see gas line sleeved / CSST supported in crawl and tied in by final
|
MEC20-00137
| Pressure Test | 2/4/2020 | 2/4/2020 | 2/4/2020 2:09:48 PM | P | PASS |
|
|
Field Super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney - 20 lb gas pressure test ok - tagged meter location
|
MEC20-00137
| Rough-in | 2/4/2020 | 2/4/2020 | 2/4/2020 2:09:23 PM | P | PASS |
|
|
Field Super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney - R/I ok
|
MEC20-00135
| Pressure Test | 2/4/2020 | 2/4/2020 | 2/4/2020 2:08:53 PM | P | FAIL |
|
|
Field super: DAryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney - gas pressure test gauge under 20lb
|
MEC20-00135
| Rough-in | 2/4/2020 | 2/4/2020 | 2/4/2020 2:07:55 PM | P | FAIL |
|
|
Field super: DAryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney - gas pressure test fail - supply and return duct work needs sealed - range hood venting needs sealed
|
MEC20-00407
| Final | 2/4/2020 | 2/4/2020 | 2/4/2020 1:38:22 PM | P | PASS |
|
|
Dan Phone #: ###-#### - final ok
|
MEC20-00421
| Final | 1/31/2020 | 2/4/2020 | 2/4/2020 1:24:15 PM | P | PASS |
|
|
Will have tech on site doing a duct cleaning --Call Zach ###-#### in route Phone #: ###-#### Inspection requested via web by Justin Osterhout - furnace ac coil co ok
|
MEC20-00487
| Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 11:30:57 AM | A | FAIL |
|
|
CALL ED 20 MIN ADVANCE TO MAKE SURE SOMEONE IS HOME FOR INSPECTOR Phone #: ###-#### Inspection requested via web by Manuel Canto - range hood ducting needs sealed - 20lb pressure test ok tagged penetration outside
|
MEC20-00358
| Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 11:03:31 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - R/I ok on both 1403 and 1405
|
MEC20-00358
| Pressure Test | 2/3/2020 | 2/4/2020 | 2/4/2020 11:03:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves 2- 5lb flue pressure tests ok on 1403
|
MEC20-00150
| Final | 2/3/2020 | 2/4/2020 | 2/4/2020 11:02:01 AM | A | CANC |
|
|
Please call prior to arrival Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - not ready schedule inspection when work is finished
|
MEC20-00150
| Rough-in | 2/4/2020 | 2/4/2020 | 2/4/2020 11:01:21 AM | A | PASS |
|
|
Please call prior to arrival Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - R/I of gas line ok - will need to see gas line penetration sealed at chimney for final schedule inspection when ready
|
MEC20-00150
| Pressure Test | 2/4/2020 | 2/4/2020 | 2/4/2020 11:00:08 AM | A | PASS |
|
|
Please call prior to arrival Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - 20lb gas pressure re test ok
|
MEC19-01155
| Final | 2/3/2020 | 2/4/2020 | 2/4/2020 10:23:07 AM | A | FAIL |
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist - need dryer tags installed on 104, 207 and 304
|
MEC20-00447
| Final | 2/3/2020 | 2/4/2020 | 2/4/2020 9:57:30 AM | A | PASS |
|
|
Please call David prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - furnace only co ok
|
MEC19-05394
| Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 9:41:23 AM | A | FAIL |
|
|
Please contact Gary Reeves to meet you at the house. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Shane Taylor - R/I not ready - need Man J submitted to City of Boise for review
|
MEC20-00484
| Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 9:12:44 AM | A | FAIL |
|
|
Rough in and gas pressure Phone #: ###-#### Inspection requested via web by santiago ramirez - 20lb gas pressure test ok - tagged meter location - fresh air duct needs backdraft damper
|
MEC20-00483
| Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 9:11:53 AM | A | FAIL |
|
|
Rough in and gas pressure inspection Phone #: ###-#### Inspection requested via web by santiago ramirez - 20lb gas pressure test fail gauge would not zero - gas line needs protective coating at penetration - fresh air duct needs backdraft damper -
|
MEC20-00086
| Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 8:31:19 AM | A | PASS |
|
|
Inspection requested via web by Loren Bailey - flue test failed gauge under 5lb will need to see 5lb witness at final or reschedule a 5lb flue test before final - R/I ok
|
MEC19-01562
| Mec-Aging Inspection | 2/4/2020 | 2/4/2020 | 2/4/2020 8:02:33 AM | | PASS |
|
|
Doc Permit Expired ok
|
MEC19-01562
| DOC - Permit Expired | 2/4/2020 | 2/4/2020 | 2/4/2020 8:02:17 AM | A | PASS |
|
|
Doc Permit Expired ok
|
MEC19-00431
| Mec-Aging Inspection | 2/4/2020 | 2/4/2020 | 2/4/2020 8:01:09 AM | | PASS |
|
|
WIP
|