Inspections for the day of: Wednesday, March 20, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01042 Final3/14/20193/20/20193/20/2019 4:10:58 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC19-00438 Final3/20/20193/20/20193/20/2019 4:09:55 PMPFAIL
ANY QUESTIONS, PLEASE CALL ZAC ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt

- side wall exhaust and make up needs to be 12' AFF like the print shows.
- Exhaust and make up air needs to be functional and it looks like the electrical contractor is working on this
MEC19-01035 Rough-in3/20/20193/20/20193/20/2019 2:39:21 PMPPASS
Pressure test Phone #: ###-#### Inspection requested via web by Lynn Johnston
- R/I ok
MEC19-01035 Pressure Test3/20/20193/20/20193/20/2019 2:38:32 PMPPASS
Pressure test Phone #: ###-#### Inspection requested via web by Lynn Johnston
- 20lb gas pressure test ok
- tagged meter location
MEC19-01128 Final3/19/20193/20/20193/20/2019 2:25:13 PMPFAIL
Construction inspection access is through the back alley behind residence. Phone #: ###-#### Inspection requested via web by Dave Sorensen
- dryer duct seam needs sealed M1502.4.2/ M1601.4.1
-screws need to be removed from dryer duct M1502.4.2
- Bird screen in duct termination needs to be removed and termination needs a backdraft damper in place M1502.3
MEC19-01106 Final3/20/20193/20/20193/20/2019 1:32:45 PMPPASS
Please contact the homeowner or Richard 1hr. before arriving to allow access to the garage unit. The homeowner has requested an appointment after 1430 if possible. ###-#### Richard Jenny Han ###-#### Thank you. Phone #: ###-#### Inspection requested via web by Richard Cusimano
- furnace ac coil co ok
MEC19-00819 Pressure Test3/20/20193/20/20193/20/2019 11:34:52 AMAPASS
R/I and pressure test on gas piping ok
- will need to see tie in on existing gas line and reg set up for 5lb system/ new 10lb system for new warehouse
- no review of gas line needed prints show whats being installed
MEC19-00811 Rough-in3/20/20193/20/20193/20/2019 11:33:49 AMPPASS
rough Phone #: ###-#### Inspection requested via web by Brandon Sorensen
- R/I ok
MEC19-00332 Final3/19/20193/20/20193/20/2019 11:15:06 AMAPASS
Mechanical Final Inspection
Lane Rich ###-#### Phone #: ###-#### Inspection requested via web by PATTY KIRK
- gas piping final ok
MEC19-01078 Final3/19/20193/20/20193/20/2019 10:55:48 AMAPART
Please call on way: Casey ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- mini split ok
- it does look like an bathroom exhaust fan is being installed. I told the general contractor that a mechanical contractor needs to make the duct connections. He said he would talk with you guys about dealing with exhaust fan. Just need to make sure ducting is being installed properly
MEC19-00994 Pressure Test3/19/20193/20/20193/20/2019 10:09:41 AMAPASS
Call Don with any issues @ ###-#### Phone #: ###-#### Inspection requested via web by Angie Maguire
- 20lb gas pressure test ok
- 5lb flue pressure test ok
- tagged meter location
MEC19-00994 Rough-in3/19/20193/20/20193/20/2019 10:09:05 AMAPASS
Call Don with any issues @ ###-#### Phone #: ###-#### Inspection requested via web by Angie Maguire
- R/I ok
MEC19-00428 Final3/19/20193/20/20193/20/2019 9:56:47 AMAPASS
Lock box: 042558 Phone #: ###-#### Inspection requested via web by Dan Otero
- fireplace final ok
MEC19-01035 Rough-in3/19/20193/20/20193/20/2019 9:29:56 AMACANC
Pressure test Phone #: ###-#### Inspection requested via web by Lynn Johnston
- contractor on site said he is ready for a R/I and a pressure test and that he would contact his office to schedule afternoon inspection
MEC19-01083 Final3/19/20193/20/20193/20/2019 9:28:10 AMANH
Cody Tipton is the contact person Phone #: ###-#### Inspection requested via web by Devry King
- no access to home left notice on front door
MEC19-01119 Final3/19/20193/20/20193/20/2019 8:51:07 AMAPASS
Robert Phone #: ###-####
- final ok
MEC18-03086 Mec-Aging Inspection3/20/20193/20/20193/20/2019 8:25:13 AM DONE
Called and talked with Jim's Heating about their mechanical aging permit. Schedule inspection with homeowner if work is finished. Permit will expire after 180 day if not active. 8/20/19
MEC18-03039 Mec-Aging Inspection3/20/20193/20/20193/20/2019 8:23:22 AM DONE
Called TML and talked with Sam about their mechanical aging permit. Schedule inspection if correction have been made. Permit will expire in 180 days if not active 8/20/19