Inspections for the day of: Thursday, May 30, 2019.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-02232 Rough-in5/29/20195/30/20195/31/2019 8:27:13 AMAPASS
Please call James at ###-#### with any questions including access information if the side door is locked. Access is through the west side door. Inspection requested via web by 4 Seasons

- R/I of make up air ok
- range vent will terminate behind hood at final
MEC19-01820 Final5/23/20195/30/20195/30/2019 4:07:45 PMPPASS
Please call Peggy in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout
- furnace only co ok
MEC19-02202 Final5/28/20195/30/20195/30/2019 3:07:37 PMPPASS
Katie is tenant. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- A/C coil co ok
MEC19-02057 Final5/30/20195/30/20195/30/2019 2:41:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Michael Stimpson
- final ok
MEC19-02183 Rough-in5/30/20195/30/20195/30/2019 1:44:29 PMPPASS
Mechanical Gas Fireplace Rough in inspection. Phone #: ###-#### Inspection requested via web by Dan Otero
- fireplace R/I ok
MEC18-05290 Final5/29/20195/30/20195/30/2019 1:44:11 PMPPASS
garage code 1234 Phone #: ###-#### Inspection requested via web by Terek Worley
- final ok
MEC18-05290 Conference5/29/20195/30/20195/30/2019 1:43:48 PMPPASS
witness Duct blast test please Phone #: ###-#### Inspection requested via web by Terek Worley
- duct blast ok
MEC19-02183 Final5/30/20195/30/20195/30/2019 1:19:26 PMPCANC
Mechanical Gas Fireplace Final Inspection
Manual in kitchen drawer
Garage code is 5674 or 9378 Phone #: ###-#### Inspection requested via web by Dan Otero
MEC19-02149 Final5/29/20195/30/20195/30/2019 11:43:57 AMAPASS
Need final for one head ductless, vacant, lockbox on door code 0621, please call Brett with any questions or concerns, ###-#### Phone #: ###-#### Inspection requested via web by Brett Shannon
- mini split final ok
MEC19-00836 Pressure Test5/29/20195/30/20195/30/2019 11:21:21 AMPPASS
If questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
- 60lb gas pressure test ok on entire system
MEC18-05436 Rough-in5/29/20195/30/20195/30/2019 11:20:47 AMAPASS
GARAGE CODE: 2390
LOCK BOX: 3535 (Lock box is by tree/bush near front door) Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- R/I ok
MEC18-05436 Final5/29/20195/30/20195/30/2019 11:20:25 AMACANC
GARAGE CODE: 2390
LOCK BOX: 3535 (Lock box is by tree/bush near front door) Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- not ready for final inspection
MEC18-05436 Pressure Test5/29/20195/30/20195/30/2019 11:20:04 AMACANC
GARAGE CODE: 2390
LOCK BOX: 3535 (Lock box is by tree/bush near front door) Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- no need for a pressure test
MEC19-02069 Pressure Test5/28/20195/30/20195/30/2019 9:53:40 AMAPASS
###-#### (DAVID) Phone #: ###-#### Inspection requested via web by Mike Almanza
- underground gas line 20lb ok
- ok to back fill line
MEC19-01266 Rough-in5/29/20195/30/20195/30/2019 9:24:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by David Shartzer
- condensate lines on the mini split system needs to be a min 3/4" and approved material
- all line sets need support in the attic
- need to see range venting for r/i on north side. South side range needs one more joint sealed at the top of vent
- line set on south side is sticking out of the wall
- need access to air handler in attic
MEC19-02125 Rough-in5/29/20195/30/20195/30/2019 8:55:46 AMAFAIL
Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need approved Man J. onsite
- fresh air cant be taken from return can. Tap into the return plenum near the frunace
MEC19-02125 Pressure Test5/29/20195/30/20195/30/2019 8:54:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Arielle Hendricks
2- 5lb flue pressure tests ok
- 20lb gas pressure test ok
- tagged meter location
MEC18-01748 Mec-Aging Inspection5/30/20195/30/20195/30/2019 8:07:26 AM FAIL
Corrections still needs to be made. If ready schedule inspection with homeowner. Permit will expire at next mechanical aging inspection and permit will have to be re issued
MEC18-01762 Mec-Aging Inspection5/30/20195/30/20195/30/2019 8:02:35 AM PASS
Expired
MEC18-01762 DOC - Permit Expired5/30/20195/30/20195/30/2019 8:02:22 AMAPASS