MEC19-01279
| Final | 5/8/2019 | 5/8/2019 | 5/8/2019 4:13:55 PM | P | PASS |
|
|
final - call brad Phone #: ###-#### Inspection requested via web by Brandon Sorensen - final ok - occ card signed
|
MEC19-01884
| Final | 5/7/2019 | 5/8/2019 | 5/8/2019 3:37:13 PM | P | NR |
|
|
Please inspect later PM and call Josh on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
|
MEC19-01884
| Pressure Test | 5/7/2019 | 5/8/2019 | 5/8/2019 3:36:17 PM | P | NR |
|
|
Please inspect later PM and call Josh on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
|
MEC19-01907
| Final | 5/8/2019 | 5/8/2019 | 5/8/2019 3:30:54 PM | P | FAIL |
|
|
Please call Ryan once on site at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lea Briggs - where chimney liner changes to rigid pipe, vent needs to be double wall b vent and cap per man. specs - will want to see connection at furnace at next inspection
|
MEC19-01844
| Final | 5/6/2019 | 5/8/2019 | 5/8/2019 2:44:44 PM | P | PASS |
|
|
Homeowner Dorian Lewis ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - furnace ac coil co ok
|
MEC19-01545
| Final | 5/7/2019 | 5/8/2019 | 5/8/2019 2:32:20 PM | P | FAIL |
|
|
Call Joey @ ###-#### prior to arrival Final inspection for furnace change out. Phone #: ###-#### Inspection requested via web by Joey Hickman - gas line at furnace needs a sediment trap installed after shut off - door into mech room needs to be weather stripped and self closing - A/C power whip needs to be weather tight conduit and line set needs some arma flex insulation installed with UV protection
|
MEC19-01697
| Rough-in | 5/8/2019 | 5/8/2019 | 5/8/2019 2:12:05 PM | P | PASS |
|
|
GALE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza - fireplace R/I ok
|
MEC19-01882
| Final | 5/6/2019 | 5/8/2019 | 5/8/2019 1:35:46 PM | P | PASS |
|
|
Contact Aaron (QHC) @ ###-#### or homeowner @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley - furnace ac coil co ok
|
MEC19-01898
| Final | 5/7/2019 | 5/8/2019 | 5/8/2019 1:09:47 PM | P | PASS |
|
|
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - furnace ac coil co ok
|
MEC19-01700
| Rough-in | 5/7/2019 | 5/8/2019 | 5/8/2019 11:46:15 AM | A | CANC |
|
|
PARTIAL Phone #: ###-#### Inspection requested via web by Oleg Chervak - pre rock R/I has already been done. Not sure what inspection was needed here. Talked with Montey and he was unsure what was being schedule here aswell
|
MEC19-01897
| Final | 5/7/2019 | 5/8/2019 | 5/8/2019 11:04:28 AM | A | PASS |
|
|
Client prefers after 9am if possible. Seeing Lisa Chipman- ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby - furnace only co ok
|
MEC19-01845
| Rough-in | 5/7/2019 | 5/8/2019 | 5/8/2019 10:47:44 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft - fireplace in back bedroom need install manual pulled out of fireplace glass - vapor barrier is touching vent - need to see finish material installed around fireplace - second fireplace needs to be roughed in aswell
|
MEC19-00558
| Pressure Test | 5/7/2019 | 5/8/2019 | 5/8/2019 9:58:59 AM | A | PASS |
|
|
through attic call for access // Randy Phone #: ###-#### - 5lb flue pressure test ok - 20lb gas pressure test ok - need to see secondary condensate drain fixed on west unit for final and gas line penetration sealed
|
MEC19-00559
| Pressure Test | 5/7/2019 | 5/8/2019 | 5/8/2019 9:51:28 AM | A | PASS |
|
|
Call for access // Randy Phone #: ###-#### - 5lb flue pressure test ok - need to see sediment trap installed after shut off valve for final
|
MEC19-01835
| Pressure Test | 5/7/2019 | 5/8/2019 | 5/8/2019 9:25:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Scott Wickstrom - 20lb gas pressure test ok
|
MEC19-00808
| Final | 5/8/2019 | 5/8/2019 | 5/8/2019 9:15:12 AM | A | PASS |
|
|
Call Dilan 20 min in advance to meet inspector Thanks Phone #: ###-#### Inspection requested via web by Manuel Canto - final ok
|
MEC19-01279
| Final | 5/7/2019 | 5/8/2019 | 5/8/2019 8:48:11 AM | A | FAIL |
|
|
final - call mike Phone #: ###-#### Inspection requested via web by Brandon Sorensen - line set penetration needs sealed - line set needs UV protection applied - make up damper has power when exhaust is turned on but doesn't open
|
MEC18-04608
| Mec-Aging Inspection | 5/8/2019 | 5/8/2019 | 5/8/2019 8:13:53 AM | | DONE |
|
|
This permit has not been active since being issued on 9/21/2018. Schedule inspection with homeowner if work is finished. This permit will expire at the next aging inspection.
|
MEC17-04148
| Mec-Aging Inspection | 5/8/2019 | 5/8/2019 | 5/8/2019 8:12:25 AM | | DONE |
|
|
WIP last inspection for a final needed approval of the green report
|
MEC19-00380
| Final | 5/7/2019 | 5/8/2019 | 5/7/2019 4:58:26 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Renea Rich Inspection cancelled from web by: Renea Rich
|
MEC19-01828
| Final | 5/7/2019 | 5/8/2019 | 5/7/2019 12:07:11 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|