Inspections for the day of: Wednesday, June 19, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01924 Final6/19/20196/19/20196/19/2019 3:28:57 PMPPASS
Final - call tony Phone #: ###-#### Inspection requested via web by Brandon Sorensen
- final ok
MEC19-02262 Final6/14/20196/19/20196/19/2019 3:28:30 PMPPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 3:00 PM. Contact for Right Now is Mary ###-####
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 5lb flue ok
-furnace ac coil co ok
MEC19-01697 Final6/19/20196/19/20196/19/2019 2:17:13 PMPPASS
###-#### GALE Phone #: ###-#### Inspection requested via web by Mike Almanza
- fireplace final ok
MEC19-02094 Final6/19/20196/19/20196/19/2019 1:57:49 PMPPASS
Please call owner Pattie when in route to home she will be home after 1pm
###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd
MEC19-02482 Final6/12/20196/19/20196/19/2019 1:32:21 PMPFAIL
Please pre-call the client prior to heading out; Mr and Mrs Caldwell. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- need to provide and installed co detectors
- furnace ac coil ok
MEC19-02570 Rough-in6/18/20196/19/20196/19/2019 11:45:19 AMAPASS
Tim Phone #: ###-####
- fireplace R/I ok
MEC19-02484 Final6/12/20196/19/20196/19/2019 10:30:29 AMAFAIL
Inspection requested via web by Margie Rowe
- need to see line set UV protected and line set cover termination sealed
MEC19-02600 Rough-in6/18/20196/19/20196/19/2019 10:18:00 AMAPART
Phone #: ###-#### Inspection requested via web by Joseph Profitt
- RTU duct work ok
MIS19-00170 MEC-Final6/19/20196/19/20196/19/2019 9:32:29 AMPPASS
Josh Phone #: ###-####
- no mechanical work being done
- final ok
- signed occ card
MEC19-02601 Rough-in6/18/20196/19/20196/19/2019 9:22:49 AMAFAIL
It''s Open Phone #: ###-#### Inspection requested via web by Kim Evans
- Stamped Man J onsite
- 20lb gas pressure test fail
- water heater b vent needs 1" clearances
- range vent needs sealed
- finished crawl space( duct work, dryer vent
- line set needs supported in attic
- line set and dryer vent needs nail plates
- line set insulation needs rips fixed
- supply trunk in crawl needs insulated
- system needs fresh air installed
MEC18-03039 Mec-Aging Inspection6/19/20196/19/20196/19/2019 9:19:59 AM PASS
expire permit ok
MEC18-03039 DOC - Permit Expired6/19/20196/19/20196/19/2019 9:19:25 AMAPASS
pass
MEC19-02505 Pressure Test6/18/20196/19/20196/19/2019 8:02:40 AMACANC
Re inspect gas piping and pressure test

208 602 8083 Phone #: ###-#### >> Inspection requested via web by Mike Pearson Inspection cancelled from web by: Mike Pearson
MEC19-02262 Final6/13/20196/19/20196/14/2019 11:08:47 AMPCANC
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 1:30 PM. Contact for Right Now is Mary ###-####

Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette