Inspections for the day of: Thursday, June 28, 2018.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-01776 Final6/27/20186/28/20186/28/2018 4:00:09 PMPPASS
John ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
-gas line penetration sealed- lineset 3.5 " off ground final ok
MEC18-02476 Rough-in6/28/20186/28/20186/28/2018 3:58:45 PMPFAIL
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves
107- return needs sealed- linesets down wall need to be repaired and tape
108- linesets need to be repaired and taped
207- supply tap needs more duct seal- 4" run into walk-in closet is sagging and needs support- supply trunk in bathroom is being kinked by the ceiling framing
208- linesets need repaired and taped- supply run in hallway is kinked reposition support- liquid line on line set is touching the metal framing studs
307- supply run into dinning room has a large sag
308- supply run into the master room has a kink reposition support- supply run into bedroom 2 has a kink reposition support
MEC18-02889 Final6/27/20186/28/20186/28/2018 2:55:04 PMPPASS
PLEASE CALL HOMEOWNER PAUL @ # LISTED WHEN EN ROUTE FOR FINAL INSPECTION. HE WOULD PREFER A TIME OF 12-2 IF POSSIBLE Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
A/C coil ok- co ok
MEC17-01960 Mec-Aging Inspection6/28/20186/28/20186/28/2018 2:36:22 PM NH
left notice on front door
MEC17-03347 Final6/27/20186/28/20186/28/2018 2:26:12 PMPPASS
Please call Tobin to give as much notice as possible so he can make sure his girlfriend is home for the inspection. Phone #: ###-#### Inspection requested via web by Sheldon Lebow
- fireplace final ok
MEC18-02761 Rough-in6/26/20186/28/20186/28/2018 2:10:46 PMPNR
call 20 min advance // Joseph Phone #: ###-####- not ready hood duct not installed yet
MEC18-02984 Final6/26/20186/28/20186/28/2018 1:40:49 PMPNH
please call when you are on the way to ensure someone is home. Customers name is Nancy and her # is ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Marisa Hone- no access tried calling the number in the notes before heading to location but the number said customer was not taking phone calls at this time
MEC18-02259 Final6/26/20186/28/20186/28/2018 1:31:41 PMPNH
Phone #: ###-#### Inspection requested via web by Mary LaFayette- no access called phone number in the notes and left a message
MEC18-02993 Final6/26/20186/28/20186/28/2018 1:09:06 PMPPASS
Call Eric at ###-#### to coordinate Phone #: ###-#### Inspection requested via web by Sabrina DeHority- furnace ok - co ok
MEC17-05719 DOC - Permit Finaled6/28/20186/28/20186/28/2018 11:27:24 AMPPASS
final ok- duct blast passed- lineset taped ok- airbalance ok-
MEC17-05719 Conference6/28/20186/28/20186/28/2018 11:26:07 AMAPASS
I need to schedule a conference for 10:30. Thanks Phone #: ###-#### Inspection requested via web by Steve Canfield- duct blast pass
MEC18-03033 Rough-in6/27/20186/28/20186/28/2018 11:25:26 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- lineset needs insulation fixed- lineset needs nail plate half way down the wall
MEC18-03033 Pressure Test6/27/20186/28/20186/28/2018 11:24:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pressure test fail gauge wouldnt zero out- 5lb flue test fail gauge was below 5lb
MEC18-03046 Pressure Test6/27/20186/28/20186/28/2018 10:54:19 AMAFAIL
Kathryn Stuart, please call to give notice. Earlier is better. Phone #: ###-#### Inspection requested via web by Sheldon Lebow- 20lb gas pressure test fail gauge was below 20lb- also need to take cap off tee in between two valves tee needs to be open- black protective coating around gas flex needs to be fixed at bends and needs to be extended to fittings at the ends of gas flex
MEC17-04577 Mec-Aging Inspection6/28/20186/28/20186/28/2018 10:20:51 AM DONE
called idaho heating and air and they will schedule a final next week
MEC17-03561 Rough-in6/27/20186/28/20186/28/2018 10:15:23 AMAPART
Rough In for approval for duct wrap. Jacob is your contact. Thank you! Phone #: ###-#### Inspection requested via web by Kim Adams- duct work on 1st floor NE corner class room ok for duct wrap- call in R/I when ceiling and grilles are in place
MEC18-02974 Final6/27/20186/28/20186/28/2018 9:30:54 AMACANC
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 9:30 . Contact for Right Now is Mary ###-####
Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
MEC18-03045 Rough-in6/27/20186/28/20186/28/2018 9:26:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace R/I ok
MEC18-02255 Final6/27/20186/28/20186/28/2018 9:14:12 AMAFAIL
AM Final Inspection Needed for MWI At Airport Plaza If You Have Any Questions Contact Brad At ###-####.; Phone #: ###-#### Inspection requested via web by Karl Hestekin
- FC1and FC2 need to be finished with grilles- roof penetrations needs to be sealed- fresh air ducts for mini splits need sealed- both east and west sides of building still have ducts not sealed
MEC18-02704 Rough-in6/28/20186/28/20186/28/2018 8:47:01 AMAFAIL
Thanks, Call Max if you need anything ###-#### Inspection requested via web by Floyd Floyd Peek- need ducted returns in bedrooms or transfer air from rooms to living room where return air is located
MEC18-02974 Final6/27/20186/28/20186/27/2018 3:29:41 PMACANC
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 11:30 AM . Contact for Right Now is Mary ###-####

Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
MEC17-03347 Final6/27/20186/28/20186/27/2018 2:08:57 PMACANC
Please call Tobin to give as much notice as possible. Phone #: ###-#### >> Inspection requested via web by Sheldon Lebow Inspection cancelled from web by: Sheldon Lebow