MEC18-03059
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 4:39:09 PM | P | PASS |
|
|
Maddie ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss - furnace ac coil co ok
|
MEC18-02985
| Rough-in | 6/29/2018 | 6/29/2018 | 6/29/2018 3:46:36 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- not ready exhaust fans still need to be flexed- dryer vent needs framing done- supply boot relocation needs done- water heater flue needs a attic insulation sheild- need to see permit pulled for gas line- and need to know whats going to be done with the old fireplace
|
MEC18-01485
| DOC - Permit Finaled | 6/29/2018 | 6/29/2018 | 6/29/2018 3:40:56 PM | P | PASS |
|
|
final ok
|
MEC18-01485
| Rough-in | 6/29/2018 | 6/29/2018 | 6/29/2018 3:40:19 PM | P | PASS |
|
|
Later in the afternoon if possible. Please Call Kyle Korb @ ###-#### 30 min prior to arrival. Phone #: ###-#### Inspection requested via web by Ashley Stegemann- Framing on fire place flue ok
|
MEC18-03082
| Rough-in | 6/29/2018 | 6/29/2018 | 6/29/2018 3:00:06 PM | P | FAIL |
|
|
Ashley Phone #: ###-####- Need Man J. onsite- Cant find where dryer vent terminates- flex ducting has many kinks that need fixed- need to see access for furnace in ceiling and a platform big enough for performing service on unit M1305.1.3 appliances in attic- lineset has rips that need fixed
|
MEC18-03082
| Pressure Test | 6/29/2018 | 6/29/2018 | 6/29/2018 2:56:28 PM | P | FAIL |
|
|
Ashley Phone #: ###-####- Gauge would not zero- need inert tape at gas line penetration
|
MEC18-03060
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 2:19:02 PM | P | NR |
|
|
BLAKE ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- not ready
|
MEC18-01034
| Final | 6/27/2018 | 6/29/2018 | 6/29/2018 1:53:58 PM | P | FAIL |
|
|
please call when you are on the way. customers name is Leonard and his number is ###-#### Phone #: ###-#### Inspection requested via web by Marisa Hone- need to provide new co's for home owner- also need to change breaker size for A/C to a 25 amp
|
MEC18-03074
| Final | 6/29/2018 | 6/29/2018 | 6/29/2018 1:22:42 PM | P | PASS |
|
|
Please call Deanna Larson at ###-#### prior to inspection and when you get there, give her time to get to door. Phone #: ###-#### Inspection requested via web by Mary LaFayette - A/C coil ok - co ok
|
MEC18-02912
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 1:04:11 PM | P | NR |
|
|
DAVE ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- not ready need to change out breaker for A/C- the guys found a leak in the old furnace flue and had to change out the entire flue pipe for new
|
MEC17-03831
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 12:47:19 PM | P | FAIL |
|
|
Call homeowner sid at 208 841 5808 for access Inspection requested via web by jeff jedlick- furnace upstairs needs a drip leg installed in gas line after shut off valve
|
MEC18-02259
| Final | 6/29/2018 | 6/29/2018 | 6/29/2018 12:23:14 PM | P | PASS |
|
|
Please call Brandi Richner prior to inspection ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace and gas line ok- co ok
|
MEC18-03057
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 12:10:16 PM | P | PASS |
|
|
Josh ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- furnace ok- co ok
|
MIS18-00251
| MEC-Conference | 6/27/2018 | 6/29/2018 | 6/29/2018 11:41:40 AM | P | CANC |
|
|
talked with Justin about access to building early afternoon friday- call 20 mins ahead-###-#### Justin ; Phone #: ###-####- talked with Justin will reschedule for monday afternoon
|
MEC18-01716
| Rough-in | 6/28/2018 | 6/29/2018 | 6/29/2018 11:39:01 AM | P | PASS |
|
|
Rough-In inspection for cover. for Waxie TI. Site contact: Aaron Roberts ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical- R/I ok ready for ceiling tile- lineset for IT room needs UV protection on roof and penetration sealed- at final will want to see warehouse exhaust and large fans operating- at final will want to also see fire riser room exhaust system and heater operating
|
MEC18-01005
| Rough-in | 6/28/2018 | 6/29/2018 | 6/29/2018 11:36:12 AM | P | PASS |
|
|
Rough-In inspection for cover for Building C South (GLS). Site Contact Aaron Roberts phone# ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical mini split multi port system ok- condensate ok- R/I ok for ceiling tile- will want to see warehouse exhaust and large fans operating at final- this is the first space in building C southside- linesets on roof need UV protection and penetration sealed aswell
|
MEC18-02898
| Final | 6/25/2018 | 6/29/2018 | 6/29/2018 10:57:04 AM | A | PASS |
|
|
please call Hannah the homeowner when 30 mins in route Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace ac coil co ok
|
MEC18-03033
| Rough-in | 6/28/2018 | 6/29/2018 | 6/29/2018 10:40:13 AM | A | PASS |
|
|
PLZ LATE AM Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok
|
MEC18-03033
| Pressure Test | 6/28/2018 | 6/29/2018 | 6/29/2018 10:39:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 5lb flue pressure test ok- 20lb gas pressure test ok-
|
MEC18-03047
| Pressure Test | 6/28/2018 | 6/29/2018 | 6/29/2018 10:22:35 AM | A | PASS |
|
|
Test gauge on east side of house next to gas meter. Phone #: ###-#### Inspection requested via web by Gary Duncan- 20lb gas pressure test ok- will need to see inert tape at gas line penetration outside and penetration sealed
|
MEC18-02704
| Rough-in | 6/29/2018 | 6/29/2018 | 6/29/2018 10:12:07 AM | A | PASS |
|
|
Cold air return ducts added to bedrooms, Call Max if you need anything ###-#### Inspection requested via web by Floyd Floyd Peek- transfer air into rooms ok
|
MEC18-01485
| Rough-in | 6/28/2018 | 6/29/2018 | 6/29/2018 10:00:36 AM | A | FAIL |
|
|
Please Call Kyle Korb @ ###-#### so he can meet the inspector on site. Phone #: ###-#### Inspection requested via web by Ashley Stegemann- flue needs framed out in attic
|
MEC18-02963
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 9:58:48 AM | A | FAIL |
|
|
Edwin Phone #: ###-####- secondary drain needs piped and a wet switch- lineset penetration needs sealed both outdoor and indoor- lineset indoor needs taped and fixed of rip along full length of insulation
|
MEC18-02964
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 9:42:03 AM | A | FAIL |
|
|
Edwin Phone #: ###-####- Need secondary drain piped or a wet switch in place- lineset penetration needs sealed both outdoor and indoor- lineset insulation needs UV protection outdoors and needs to be completely taped of rips indoors
|
MEC18-02476
| Rough-in | 6/28/2018 | 6/29/2018 | 6/29/2018 9:17:26 AM | A | PASS |
|
|
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves- this included the dryer vents- R/I ok
|