Inspections for the day of: Friday, June 29, 2018.
Number of inspections: 25
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03059 Final6/28/20186/29/20186/29/2018 4:39:09 PMPPASS
Maddie ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
- furnace ac coil co ok
MEC18-02985 Rough-in6/29/20186/29/20186/29/2018 3:46:36 PMPNR
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- not ready exhaust fans still need to be flexed- dryer vent needs framing done- supply boot relocation needs done- water heater flue needs a attic insulation sheild- need to see permit pulled for gas line- and need to know whats going to be done with the old fireplace
MEC18-01485 DOC - Permit Finaled6/29/20186/29/20186/29/2018 3:40:56 PMPPASS
final ok
MEC18-01485 Rough-in6/29/20186/29/20186/29/2018 3:40:19 PMPPASS
Later in the afternoon if possible. Please Call Kyle Korb @ ###-#### 30 min prior to arrival. Phone #: ###-#### Inspection requested via web by Ashley Stegemann- Framing on fire place flue ok
MEC18-03082 Rough-in6/29/20186/29/20186/29/2018 3:00:06 PMPFAIL
Ashley Phone #: ###-####- Need Man J. onsite- Cant find where dryer vent terminates- flex ducting has many kinks that need fixed- need to see access for furnace in ceiling and a platform big enough for performing service on unit
M1305.1.3 appliances in attic- lineset has rips that need fixed
MEC18-03082 Pressure Test6/29/20186/29/20186/29/2018 2:56:28 PMPFAIL
Ashley Phone #: ###-####- Gauge would not zero- need inert tape at gas line penetration
MEC18-03060 Final6/28/20186/29/20186/29/2018 2:19:02 PMPNR
BLAKE ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- not ready
MEC18-01034 Final6/27/20186/29/20186/29/2018 1:53:58 PMPFAIL
please call when you are on the way. customers name is Leonard and his number is ###-####
Phone #: ###-#### Inspection requested via web by Marisa Hone- need to provide new co's for home owner- also need to change breaker size for A/C to a 25 amp
MEC18-03074 Final6/29/20186/29/20186/29/2018 1:22:42 PMPPASS
Please call Deanna Larson at ###-#### prior to inspection and when you get there, give her time to get to door. Phone #: ###-#### Inspection requested via web by Mary LaFayette
- A/C coil ok - co ok
MEC18-02912 Final6/28/20186/29/20186/29/2018 1:04:11 PMPNR
DAVE ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- not ready need to change out breaker for A/C- the guys found a leak in the old furnace flue and had to change out the entire flue pipe for new
MEC17-03831 Final6/28/20186/29/20186/29/2018 12:47:19 PMPFAIL
Call homeowner sid at 208 841 5808 for access Inspection requested via web by jeff jedlick- furnace upstairs needs a drip leg installed in gas line after shut off valve
MEC18-02259 Final6/29/20186/29/20186/29/2018 12:23:14 PMPPASS
Please call Brandi Richner prior to inspection ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace and gas line ok- co ok
MEC18-03057 Final6/28/20186/29/20186/29/2018 12:10:16 PMPPASS
Josh ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- furnace ok- co ok
MIS18-00251 MEC-Conference6/27/20186/29/20186/29/2018 11:41:40 AMPCANC
talked with Justin about access to building early afternoon friday- call 20 mins ahead-###-#### Justin ; Phone #: ###-####- talked with Justin will reschedule for monday afternoon
MEC18-01716 Rough-in6/28/20186/29/20186/29/2018 11:39:01 AMPPASS
Rough-In inspection for cover. for Waxie TI. Site contact: Aaron Roberts ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical- R/I ok ready for ceiling tile- lineset for IT room needs UV protection on roof and penetration sealed- at final will want to see warehouse exhaust and large fans operating- at final will want to also see fire riser room exhaust system and heater operating
MEC18-01005 Rough-in6/28/20186/29/20186/29/2018 11:36:12 AMPPASS
Rough-In inspection for cover for Building C South (GLS). Site Contact Aaron Roberts phone# ###-#### Phone #: ###-#### Inspection requested via web by RM Mechanical
mini split multi port system ok- condensate ok- R/I ok for ceiling tile- will want to see warehouse exhaust and large fans operating at final- this is the first space in building C southside- linesets on roof need UV protection and penetration sealed aswell
MEC18-02898 Final6/25/20186/29/20186/29/2018 10:57:04 AMAPASS
please call Hannah the homeowner when 30 mins in route Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace ac coil co ok
MEC18-03033 Rough-in6/28/20186/29/20186/29/2018 10:40:13 AMAPASS
PLZ LATE AM Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok
MEC18-03033 Pressure Test6/28/20186/29/20186/29/2018 10:39:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 5lb flue pressure test ok- 20lb gas pressure test ok-
MEC18-03047 Pressure Test6/28/20186/29/20186/29/2018 10:22:35 AMAPASS
Test gauge on east side of house next to gas meter. Phone #: ###-#### Inspection requested via web by Gary Duncan- 20lb gas pressure test ok- will need to see inert tape at gas line penetration outside and penetration sealed
MEC18-02704 Rough-in6/29/20186/29/20186/29/2018 10:12:07 AMAPASS
Cold air return ducts added to bedrooms, Call Max if you need anything ###-#### Inspection requested via web by Floyd Floyd Peek- transfer air into rooms ok
MEC18-01485 Rough-in6/28/20186/29/20186/29/2018 10:00:36 AMAFAIL
Please Call Kyle Korb @ ###-#### so he can meet the inspector on site. Phone #: ###-#### Inspection requested via web by Ashley Stegemann- flue needs framed out in attic
MEC18-02963 Final6/28/20186/29/20186/29/2018 9:58:48 AMAFAIL
Edwin Phone #: ###-####- secondary drain needs piped and a wet switch- lineset penetration needs sealed both outdoor and indoor- lineset indoor needs taped and fixed of rip along full length of insulation
MEC18-02964 Final6/28/20186/29/20186/29/2018 9:42:03 AMAFAIL
Edwin Phone #: ###-####- Need secondary drain piped or a wet switch in place- lineset penetration needs sealed both outdoor and indoor- lineset insulation needs UV protection outdoors and needs to be completely taped of rips indoors
MEC18-02476 Rough-in6/28/20186/29/20186/29/2018 9:17:26 AMAPASS
107,108,207,208,307,308 Phone #: ###-#### Inspection requested via web by Gary Reeves- this included the dryer vents- R/I ok