Inspections for the day of: Tuesday, July 10, 2018.
Number of inspections: 29
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03206 Final7/6/20187/10/20187/10/2018 4:30:21 PMPPASS
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC18-02793 Final7/6/20187/10/20187/10/2018 3:39:01 PMPPASS
Call Susan when in route ###-#### --She is not home until after 1PM Phone #: ###-#### Inspection requested via web by Justin Osterhout
- furnace change out ok- co ok
MEC18-03095 Final7/9/20187/10/20187/10/2018 2:37:41 PMPFAIL
Phone #: ###-#### Inspection requested via web by Mary LaFayette- need a wet switch on indoor coil- need to strap up/support lineset in basement- fix rip along lineset near indoor coil- provide new co detectors near bedrooms
MEC18-03252 Final7/10/20187/10/20187/10/2018 2:23:58 PMPNH
Please call on way: Gener ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- no access to home
MEC18-03252 Pressure Test7/10/20187/10/20187/10/2018 2:23:40 PMPNH
Please call on way: Gener ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- no access to home
MEC18-02476 Rough-in7/10/20187/10/20187/10/2018 2:15:50 PMPNR
105and 106 crawl not ready- some flex runs need supported- flex duct being smashed- line set insulation needs repaired and needs nail plates at floor-205 and 206 one lineset needs fire caulked at floor- some duct sealing needs finished- duct work is being smashed by ceiling and some flex runs need support- 305 and 306 flex duct needs rerouted and supports need adjusted flex ducting should be ran free or kinks or smashes and free flowing bends
MEC17-05457 Pressure Test7/10/20187/10/20187/10/2018 12:34:21 PMPPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- 60 lb gas pressure test for gas line from west end of building through garage,and into kitcken area and down the walls for gas range ok, gas line stops in kitcken for now but will extend further into building later- wall cover in kitcken area ok- need one more set of supports on gas line above ceiling
MEC18-02618 Rough-in7/10/20187/10/20187/10/2018 12:27:10 PMPCANC
Late PM. We are fixing this today in the afternoon, so please call before arrival: Gener ###-#### Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
MEC18-01559 Final7/10/20187/10/20187/10/2018 12:03:22 PMPNR
AC: 2018 Phone #: ###-#### Inspection requested via web by Gary Reeves- not ready still need exhaust fans, lineset supported, range exhaust, gasline to water heater
MEC18-01486 Final7/9/20187/10/20187/10/2018 12:02:02 PMPPASS
Please Call Kyle Korb at ###-#### when on the way.
Reference 3/5 young mdw. Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace final ok
MEC18-03204 Final7/9/20187/10/20187/10/2018 11:48:54 AMAPASS
ON SITE CONTACT: TERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil ok
MEC18-03217 Final7/10/20187/10/20187/10/2018 11:32:18 AMPPASS
Electrical Permit has been pulled. Phone #: ###-#### Inspection requested via web by Krista Boss- electrical permit was pulled mech final ok
MEC17-03561 Rough-in7/10/20187/10/20187/10/2018 11:30:21 AMPPART
Approval for cover ; hard lids - special ED 1st floor - Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- 102 exhaust duct seal ok, need to see one more strap placed on duct, need to also see access door in place for exhaust fan, ducting for kitchen exhaust hood is ran up into 205 duct seal ok, need to see framing in room 205 and where the duct will penetrate roof - 107 not ok for cover need to see flex duct straped and rerouted in three rooms, need to start seeing that the inner liner of the flex is being taped aswell- 108 exhaust and transfers ducts sealed and ok for cover- call in AM and i will come check room 107 for hardlid cover
MEC18-02476 Rough-in7/9/20187/10/20187/10/2018 11:23:30 AMPCANC
please inspect 105,106,205,206,305 and 306 Phone #: ###-#### Inspection requested via web by Gary Reeves-
MEC18-03212 Rough-in7/9/20187/10/20187/10/2018 10:47:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Sheldon Lebow- fireplace flue and insulation sheild ok
MEC18-03124 Final7/3/20187/10/20187/10/2018 10:42:39 AMPPASS
INSTALLER JESSE ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC17-02128 Mec-Aging Inspection7/10/20187/10/20187/10/2018 10:27:33 AM DONE
called total systems services to schedule inspection with homeowner
MEC18-03237 Pressure Test7/9/20187/10/20187/10/2018 10:23:22 AMAFAIL
Owner contact information - Gae Peyron - ###-#### Phone #: ###-#### Inspection requested via web by Jamee Shoecraft-- gasline outside is laying on the ground needs to be supported and 3.5" off the ground- Flex gas line in the fireplace needs black protective coating extended to fitting bare flex can't be showing. this is the case at the outdoor connection aswell- need double valve with open ended tee between the two valves at the tie in location near the meter
MEC17-03454 Mec-Aging Inspection7/10/20187/10/20187/10/2018 9:39:20 AM DONE
called Grant to have him schedule with homeowner
MEC18-03039 Final7/6/20187/10/20187/10/2018 9:33:47 AMAFAIL
can you please call when you are on the way customers name is Jackie and her # is ###-#### Phone #: ###-#### Inspection requested via web by Marisa Hone- lineset at indoor unit was touching flue, strap lineset to duct work behind flue- need to also tape lineset rip right at indoor coil
MEC17-03831 Final7/9/20187/10/20187/10/2018 9:13:36 AMAPASS
Inspection requested via web by jeff jedlick- drip leg in gas line upstairs ok- both furnace ac coil co ok
MEC18-02700 Final7/9/20187/10/20187/10/2018 9:00:41 AMAFAIL
call when you are on the way please... customers name is Lisa and her number is ###-#### Phone #: ###-#### Inspection requested via web by Marisa Hone- A/C breaker is over sized needs to be a 20amp and its a 30amp
MEC18-01512 Final7/9/20187/10/20187/10/2018 8:40:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Sheldon Lebow- fireplace final ok - garage 2425
MEC18-03159 Rough-in7/9/20187/10/20187/10/2018 8:04:48 AMACANC
Geff Phone #: ###-####- shouod have been a final. cloned inspection into a final A/C coil ok
MEC18-03159 Final7/10/20187/10/20187/10/2018 8:04:03 AMAPASS
Geff Phone #: ###-#### lineset supported A/C coil ok
MEC18-03090 Final7/10/20187/10/20187/10/2018 8:02:01 AMPCANC
Kelly Buel is tech on-site. requesting early pm gas pressure test Phone #: ###-#### >> Inspection requested via web by kelly Martin Inspection cancelled from web by: kelly Martin
MEC18-02618 Rough-in7/9/20187/10/20187/9/2018 4:53:13 PMACANC
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
MEC18-02700 Final7/6/20187/10/20187/9/2018 10:30:01 AMPCANC
if possible can you please call on the way Phone #: ###-#### >> Inspection requested via web by Marisa Hone Inspection cancelled from web by: Marisa Hone
MEC18-03205 Final7/6/20187/10/20187/6/2018 9:22:55 AMPCANC
INSTALLER TRAVIS ###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt