MEC19-01845
| Rough-in | 7/10/2019 | 7/10/2019 | 7/10/2019 4:12:02 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft 2- fireplaces R/I ok
|
MEC19-01280
| Rough-in | 7/9/2019 | 7/10/2019 | 7/10/2019 4:11:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Arielle Hendricks - R/I ok
|
MEC19-02949
| Final | 7/10/2019 | 7/10/2019 | 7/10/2019 3:09:23 PM | P | PASS |
|
|
Final inspection. ACS contact Wayne ###-#### our job 42008. Phone #: ###-#### Inspection requested via web by Kathy Youngkin - final ok
|
MEC19-02945
| Final | 7/10/2019 | 7/10/2019 | 7/10/2019 3:09:11 PM | P | PASS |
|
|
Final inspection. ACS Contact is Wayne ###-####. Our job 41980. Phone #: ###-#### Inspection requested via web by Kathy Youngkin - final ok
|
MEC19-02923
| Final | 7/10/2019 | 7/10/2019 | 7/10/2019 2:32:53 PM | P | FAIL |
|
|
Call ahead // Tim - Apt 2 Phone #: ###-#### - A/C conduit needs to be weather tight
|
MEC19-01700
| Rough-in | 7/10/2019 | 7/10/2019 | 7/10/2019 2:08:48 PM | P | PASS |
|
|
PART Phone #: ###-#### Inspection requested via web by Oleg Chervak - south side duct seal and R/I ok - R/I ok
|
MEC19-01535
| Final | 7/9/2019 | 7/10/2019 | 7/10/2019 2:07:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lynn Johnston - final ok
|
MEC19-02943
| Rough-in | 7/10/2019 | 7/10/2019 | 7/10/2019 1:51:38 PM | P | PASS |
|
|
call Erick super from contractor to either meet inspector and open door or make sure someone is at the premises. thanks. Phone #: ###-#### Inspection requested via web by Manuel Canto - 20lb gas pressure test ok - R/I ok
|
MEC19-00240
| Pressure Test | 7/10/2019 | 7/10/2019 | 7/10/2019 12:55:16 PM | P | NR |
|
|
Contact: Craig Lacy ###-#### Phone #: ###-#### Inspection requested via web by Brent Lacy - not ready talked with Gustavo and rescheduled with him tomorrow morning
|
MEC19-02935
| Final | 7/9/2019 | 7/10/2019 | 7/10/2019 12:50:22 PM | P | FAIL |
|
|
Please have inspector call the owner Sally when in route to home ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd - need to provide weather stripping around door to seal off closet for furnace, self closing device and all combustion air coming from the outside. - install sediment trap on gas line to furnace
|
MEC19-02782
| Rough-in | 7/10/2019 | 7/10/2019 | 7/10/2019 12:37:48 PM | P | FAIL |
|
|
Michael- please call for access. Phone #: ###-#### - gas line to range upstairs still needs proper striker plates installed. gas line is less than 2" away from stud edge
|
MEC18-03731
| Mec-Aging Inspection | 7/10/2019 | 7/10/2019 | 7/10/2019 8:33:01 AM | | DONE |
|
|
Doc permit expired
|
MEC18-03731
| DOC - Permit Expired | 7/10/2019 | 7/10/2019 | 7/10/2019 8:32:46 AM | A | PASS |
|
|
-Permit has not been active since being issued - Doc permit expired ok
|
MEC19-01283
| Pressure Test | 7/9/2019 | 7/10/2019 | 7/9/2019 3:04:16 PM | P | CANC |
|
|
AC: 0906 Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
MEC19-01283
| Final | 7/9/2019 | 7/10/2019 | 7/9/2019 3:04:14 PM | P | CANC |
|
|
AC: 0906 Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
MEC19-01280
| Pressure Test | 7/8/2019 | 7/10/2019 | 7/9/2019 10:16:54 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
|
MEC19-01280
| Rough-in | 7/8/2019 | 7/10/2019 | 7/9/2019 10:16:52 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
|