Inspections for the day of: Monday, August 12, 2019.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03455 Pressure Test8/6/20198/12/20198/12/2019 3:51:36 PMPPASS
PLEASE CALL PLUMBER ZAK GREEN WHEN ON THE WAY. THANK YOU Phone #: ###-#### Inspection requested via web by Chris Field
- 20lb gas pressure test ok
MEC19-00240 Pressure Test8/12/20198/12/20198/12/2019 3:36:21 PMPPASS
Contact: Robert Church ###-####. Phone #: ###-#### Inspection requested via web by Brent Lacy
- 20lb gas pressure test on 206,202 ,101,102,107 units ok
MEC19-00240 Pressure Test8/12/20198/12/20198/12/2019 3:35:12 PMPPASS
3rd floor hydronics // Robert Phone #: ###-####
- 3rd floor 100lb hydronics main ok
MEC19-02654 Final8/9/20198/12/20198/12/2019 2:32:32 PMPFAIL
Please inspect after 3:30 and call landlord, Kelly, prior to inspection so he can meet you there. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- need to install co detector near bedrooms
MEC19-03362 Final8/9/20198/12/20198/12/2019 2:07:11 PMPFAIL
Please call Barbra on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need to see electrical permit for relocation of A/C
- need co detectors installed upstairs and downstairs
- line set at indoor unit has a kink at the floor and is missing insulation
MEC19-02852 Final8/12/20198/12/20198/12/2019 1:47:03 PMPPART
this is a "partial final" inspection. No one from Trane will be onsite so please call with any questions. Thank you. Phone #: ###-#### Inspection requested via web by Crystal Grant
- phase 1 parial final ok will receive full final when the rest of the remodel is finished
MEC19-03476 Rough-in8/12/20198/12/20198/12/2019 1:19:43 PMPPASS
Mechanical Gas Fireplace Rough-in Inspection Phone #: ###-#### Inspection requested via web by Dan Otero
- fireplace R/I ok
MEC19-02879 Rough-in8/11/20198/12/20198/12/2019 1:11:00 PMPPASS
Phone #: ###-#### Inspection requested via web by yuriy kryachun
- R/I ok
- plumbing vent going through roof needs to be extended 3' above fresh air on unit downstairs
- contractor will pipe out combustion air for both furnaces for final
-
-
MEC19-02879 Pressure Test8/11/20198/12/20198/12/2019 1:09:03 PMPPASS
Phone #: ###-#### Inspection requested via web by yuriy kryachun
2- 5lb flue pressure tests ok
-20lb gas pressure test ok
- tagged meter location
MEC19-03508 Rough-in8/9/20198/12/20198/12/2019 12:48:30 PMACANC
access code for key lockbox is 9811. Phone #: ###-#### Inspection requested via web by Steve Canfield
- went to suite 100 which was cold chain and the lady at the front desk didn't know about any work being done. tried calling Steve with contractor and no answer. It seems that this permit was pulled on the wrong address maybe. reschedule with more information
MEC19-02967 Final8/7/20198/12/20198/12/2019 12:28:29 PMAFAIL
Please call RAmiro on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- common b vent needs 1" clearances at wall
MEC19-03442 Rough-in8/9/20198/12/20198/12/2019 11:26:50 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- need access to furnace model numbers
- water flue has screws through inner pipe
- return duct upstairs needs sealed
- fix return flex outter liner upstairs
- line set in crawl need supported and rips fixed
- fresh air needs to be installed at furnace return plenum
- nail plates at dryer vent and pvc flue
- 5lb flue test fail
- support gas line in attic near range
MEC19-03442 Pressure Test8/9/20198/12/20198/12/2019 11:24:01 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jon VanderStelt
- 5lb flue pressure test under 5lb
- 20lb gas pressure test ok
- tagged meter location
MEC19-03300 Final8/9/20198/12/20198/12/2019 10:57:33 AMPPASS
Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- final ok
MEC19-03553 Pressure Test8/12/20198/12/20198/12/2019 10:56:57 AMAPASS
Home #4. Exterior, North side yard. New exterior gas and home both under pressure test. Sean is the contact. Phone #: ###-#### Inspection requested via web by Scott Sparrell
- 20lb under ground ok backfill ok
- 20lb gas in home ok
- tagged meter location
- will need to see flex line installed for final
MEC19-01022 Final8/7/20198/12/20198/12/2019 10:37:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- final ok
MEC19-00346 Rough-in8/9/20198/12/20198/12/2019 10:32:22 AMAFAIL
albert Phone #: ###-####
- right side wall has combustibles within 18" of
hood
- all 3 exhaust fans needs extensions installed
-pressure test needs to be 60lb
-gas lines on roof need sediment traps and test ports
- roof caps need sealed
-make up air duct needs insulated and installed per prints
-need to see electrical permit pulled
- equipment needs to be 6" inside hood
- seams on backside and left side of hood need sealed
MEC19-03364 Final8/7/20198/12/20198/12/2019 8:30:11 AMACANC
Call technician Juan when you are on the way to have him meet you onsite for access. Phone #: ###-#### Inspection requested via web by Misty McNabb
- no access reschedule
MEC19-03422 Pressure Test8/9/20198/12/20198/12/2019 7:57:02 AMAPASS
Jack already took care of this this morning. I forgot to call it in like I was supposed to. Please connect with him on this and/or give me a buzz. -Alyssa Phone #: ###-#### Inspection requested via web by Alyssa Cromwell
- 5lb flue pressure test ok
MEC19-03422 Final8/12/20198/12/20198/12/2019 7:56:35 AMAPASS
Jack already took care of this this morning. I forgot to call it in like I was supposed to. Please connect with him on this and/or give me a buzz. -Alyssa Phone #: ###-#### Inspection requested via web by Alyssa Cromwell
- furnace only co ok