Inspections for the day of: Friday, August 30, 2019.
Number of inspections: 27
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03107 Final8/30/20198/30/20198/30/2019 4:18:48 PMPFAIL
call for lockbox code if necessary // Izzy Phone #: ###-####
- need to see clearances on unit heater flues and paint booth exhaust duct
- unit heater needs 18" service clearances
- unit heaters need a concentric kit or two pipe system for combustion
- flues on roof need supported
- seismic bracing of unit heaters
- this should have been a R/I inpsection
- will need to see balance report of system for final
MEC19-03107 Pressure Test8/30/20198/30/20198/30/2019 4:13:59 PMPPASS
call for lockbox code if necessary // Izzy Phone #: ###-####
- 60 lb gas pressure test ok
- tagged meter location
MEC19-00216 Final8/29/20198/30/20198/30/2019 4:12:41 PMPFAIL
I will be there between 12PM and 3PM for access Phone #: ###-#### Inspection requested via web by Doug Turner
- mc jacketed cable needs UL listed connectors and to be weather tight
MEC19-03657 Final8/23/20198/30/20198/30/2019 2:57:09 PMPFAIL
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace only co ok
- need to see an electrical permit
MEC19-03878 Final8/30/20198/30/20198/30/2019 2:33:44 PMPFAIL
Tony Phone #: ###-####
- need to see CO detector installed in hallway near bedrooms
- A/C breaker needs to be a 25amp
- also need to see electrical permit pulled for new wiring to A/C
MEC19-03887 Pressure Test8/29/20198/30/20198/30/2019 2:01:10 PMPPASS
INSTALLER KYLE ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- 60lb gas and 20lb gas pressure test ok
- tagged meter location
- ok for back fill
MEC19-03530 Rough-in8/30/20198/30/20198/30/2019 1:38:11 PMPCANC
MEC19-03529 Rough-in8/30/20198/30/20198/30/2019 1:37:58 PMPCANC
MEC19-03531 Pressure Test8/30/20198/30/20198/30/2019 1:21:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by Debbie Marino
- gauge wont zero
MEC19-03531 Rough-in8/30/20198/30/20198/30/2019 1:21:09 PMPFAIL
Phone #: ###-#### Inspection requested via web by Debbie Marino
-line set insulation needs rips fixed
- gas pressure test fail gauge wont zero
MEC19-03898 Pressure Test8/30/20198/30/20198/30/2019 12:26:10 PMPPASS
Can you call at the number above, if there are any issues?

Nat Phone #: ###-#### Inspection requested via web by Nat Golden
- 20lb gas pressure test ok
- tagged meter location
MEC19-03897 Pressure Test8/30/20198/30/20198/30/2019 12:25:35 PMPPASS
Can you call Tom at the number above, if there are any issues?

Nat Phone #: ###-#### Inspection requested via web by Nat Golden
- 20lb gas pressure test ok
- tagged meter location
MEC19-03736 Rough-in8/29/20198/30/20198/30/2019 11:54:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- frame out needs to be per specs 43 3/8"
- side clearances need to be 3/4"
- non combustibles installed above fireplace
need to see gas line installed
MEC19-01790 Rough-in8/29/20198/30/20198/30/2019 11:21:37 AMAFAIL
Mechanical Ceiling Grid inspection needed if you have any questions please contact Karl at ###-#### Inspection requested via web by Karl Hestekin
- line set insulation through out needs finished
- several locations above ceiling grid need duct seal finished
- one unit need condensate line finished by others
MEC19-03802 Conference8/23/20198/30/20198/30/2019 10:58:29 AMADONE
Checking to make sure I''m not missing any details.
Thank you Phone #: ###-#### Inspection requested via web by Thomas Dubert
MEC19-03080 Final8/30/20198/30/20198/30/2019 9:59:07 AMPPASS
If there are any issues, can you call Tom at this number?

Thanks,
Nat Phone #: ###-#### Inspection requested via web by Nat Golden
- gas line final ok
MEC19-03522 Final8/29/20198/30/20198/30/2019 9:52:25 AMAPASS
Jasper will be on site at 9:20. Please contact him with any questions. Phone #: ###-#### Inspection requested via web by Ted Dumont
- 5lb flue pressure test ok
- furnace ac coil co ok
MEC19-03726 Pressure Test8/29/20198/30/20198/30/2019 9:36:54 AMAPASS
Gauge outside Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 20lb gas pressure test ok
- tagged meter location
MEC19-03744 Pressure Test8/29/20198/30/20198/30/2019 9:30:43 AMAPASS
I''ll be working across the street. Please call me for access to witness pressure test on exhaust line. Phone #: ###-#### Inspection requested via web by terry Warden
- 5lb flue pressure test of tankless water heater relocate ok
MEC19-02601 Final8/28/20198/30/20198/30/2019 9:29:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Kim Evans-call for access code
- final ok
MEC18-03082 Final8/29/20198/30/20198/30/2019 8:43:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- no access to home left notice on front door
MEC19-03888 Pressure Test8/29/20198/30/20198/30/2019 8:32:36 AMAPASS
Please call homeowner Laura @ ###-#### when en route Phone #: ###-#### Inspection requested via web by Rusty Karel
- 20lb gas pressure test ok
MEC19-00266 Final8/29/20198/30/20198/30/2019 8:13:25 AMAPASS
Jake is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist
- final ok
- Occ card will be signed when other mechanical permit passes final inspection
MEC19-02587 Final8/30/20198/30/20198/30/2019 7:57:34 AMAPASS

Phone #: ###-#### Inspection requested via web by Michael Stimpson
- final ok
MEC19-00299 Mec-Aging Inspection8/30/20198/30/20198/30/2019 7:56:52 AM FAIL
Schedule final inspection of fireplace with homeowner. Permit has not been active since 1/25/19 when it passed R/I inspection.
MEC19-00313 Mec-Aging Inspection8/30/20198/30/20198/30/2019 7:55:26 AM PASS
Doc Permit Final ok
MEC19-00313 DOC - Permit Finaled8/30/20198/30/20198/30/2019 7:55:13 AMAPASS
Doc Permit Final ok