Inspections for the day of: Monday, September 17, 2018.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-04507 Rough-in9/17/20189/17/20189/17/2018 4:37:04 PMPFAIL
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak
- line set has rip in the insulation at the top of the wall
-supply trunk in the attic needs insulated
-crawl not finished
-insulation sheild in the attic for the water heater need to be centered around the pipe to maintain 1" clearances
-fire caulk around fireplace vent needs to be sealed
-fresh air for the furnace is terminating out the soffit and will need a fire damper or terminate side wall( WUI Zone A)
- flex runs need to be installed per Manuf. spec the inner liner needs to be taped and the outer liner needs to be zip tied. One of the flex runs for an exhaust fan was not connected and not sealed with tape
MEC18-04507 Pressure Test9/17/20189/17/20189/17/2018 4:25:05 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pressure test ok
MEC18-04298 Rough-in9/17/20189/17/20189/17/2018 3:59:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC18-00675 Final9/10/20189/17/20189/17/2018 2:59:26 PMPFAIL
Please call John 30 min prior to arrival Phone #: ###-#### Inspection requested via web by Andrea Grigsby- need 1" clearances around b vent and ceiling- need to install co detectors upstairs near bedrooms and the co detector downstairs need to be in the hallway not the laundry room
MEC18-04447 Final9/12/20189/17/20189/17/2018 2:44:49 PMPPASS
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace ac coil co ok
MEC18-03574 Final9/17/20189/17/20189/17/2018 2:36:27 PMPPASS
Contact: Robert Church ###-#### Phone #: ###-#### Inspection requested via web by Brent Lacy- gas piping final ok
MEC18-04465 Final9/14/20189/17/20189/17/2018 2:28:57 PMPFAIL
Phone #: ###-#### Inspection requested via web by Mary LaFayette- need a drip leg after shut off valve on gas line- b vent needs 1" clearances to duct work insulation at furnace
MEC17-01386 Rough-in9/17/20189/17/20189/17/2018 2:08:52 PMPFAIL
Scott Phone #: ###-####- dryer vent needs to be smooth pipe- water heater needs 3" clearances on horizantal runs and 1" clearances on vertical- condensates need to be finished- there is also two more ductless splits that need installed for R/I cover-southside still has an exhaust fan that needs vented and a ductless split that needs condensate finished- need to look into the HVAC contractors permit for the multiport ductless that is finished-
MEC17-04462 Mec-Aging Inspection9/17/20189/17/20189/17/2018 10:33:15 AM CANC
MEC16-04910 Mec-Aging Inspection9/17/20189/17/20189/17/2018 10:32:35 AM DONE
while talking with the homeowner during the fireplace final he said there was still some work being done on other half of the house- WIP
MEC18-04460 Rough-in9/15/20189/17/20189/17/2018 10:23:19 AMANR
house is vacancy lock box #5134 Phone #: ###-#### Inspection requested via web by thomas nguyen- corrections were made and are ok- need to see the water heater b vent fastened down so that 1" clearances are maintained- also want to see wall framed in that the dryer vent runs into
MEC18-03759 Final9/11/20189/17/20189/17/2018 10:05:38 AMAPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 10:00 AM. Contact for Right Now is Mary ###-####

Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 5lb flue pressure test ok- furnace only co ok
MEC18-04049 Rough-in9/14/20189/17/20189/17/2018 9:45:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace R/I ok- still need to see gasline R/I to fireplace do not cover until gasline has been inspected
MEC18-04298 Rough-in9/14/20189/17/20189/17/2018 9:13:16 AMAFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves- water heater flue needs a insulation sheild in the attic- would like to see clearances on the b vent for the water heater in the attic- where the flue turns a 90 elbow in the attic is hard to see clearances to combustilbes
MEC18-04298 Pressure Test9/14/20189/17/20189/17/2018 9:11:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pressure test ok- 5lb flue pressure test ok
MEC18-04482 Pressure Test9/14/20189/17/20189/17/2018 7:15:28 AMACANC
Thanks >> Inspection requested via web by Floyd Floyd Peek Inspection cancelled from web by: Floyd Floyd Peek
MEC18-04482 Rough-in9/14/20189/17/20189/17/2018 7:15:22 AMACANC
>> Inspection requested via web by Floyd Floyd Peek Inspection cancelled from web by: Floyd Floyd Peek