Inspections for the day of: Friday, September 27, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03926 Final9/25/20199/27/20199/27/2019 3:27:37 PMPFAIL
Please inspect as late as possible and call prior. Davis Weymann ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- need refrigerant locking caps at outdoor unit
- seal line set penetration
- secondary drain needs wet switch
- cant read fuse rating in service disconnect
MEC19-02782 Final9/27/20199/27/20199/27/2019 3:20:19 PMPFAIL
Michael Phone #: ###-####
- need UL listed weather tight connectors for MC cables
- range venting needs a back draft damper
MEC19-03370 Final9/26/20199/27/20199/27/2019 2:57:02 PMPPASS
Please call owner :Debbie Wachtell ###-#### before heading her way, thank you.
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- furnace ac coil co ok
MEC19-04178 Final9/27/20199/27/20199/27/2019 2:38:50 PMPPASS
- furnace only co ok
MEC19-02852 Final9/26/20199/27/20199/27/2019 2:04:11 PMPPASS
This is a rough-in final. Final inspection for project will be scheduled after air balance which will be next week. Call Glen with any questions. Phone #: ###-#### Inspection requested via web by Yvonne Bowman
- final ok
MEC19-04178 Final9/25/20199/27/20199/27/2019 1:07:40 PMPNH
Jared Patchin is requesting the final inspection after 1pm if at all possible Phone #: ###-#### Inspection requested via web by Devry King
- no access to home left notice on front door
MEC19-04230 Final9/25/20199/27/20199/27/2019 11:59:27 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kyle Flanagan
- need to install sediment trap on furnace gas line
- owner says water heater is getting changed out next week. Need to see a plumbing permit pulled for water heater
MEC19-04216 Final9/24/20199/27/20199/27/2019 10:17:23 AMAPASS
Please call Donna Prior to arrival, prefers in the morning. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- furnace only co ok
MEC19-03008 Final9/24/20199/27/20199/27/2019 9:54:46 AMAFAIL
Builder Contact: Jason ###-####
HVAC Contact: Daniel ###-####
Access Instructions: On the far left house, on the backside of a pillar on the front porch, there’s a
lockbox (9165), There are three keys inside; green goes to the middle house, the bare keys work on other two. Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need duct blast report onsite
MEC19-03007 Final9/24/20199/27/20199/27/2019 9:54:15 AMAFAIL
Builder Contact: Jason ###-####
HVAC Contact: Daniel ###-####
Access Instructions: On the far left house, on the backside of a pillar on the front porch, there’s a lockbox (9165), There are three keys inside; green goes to the middle house, the bare keys work on other two. Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need duct blast report onsite
MEC19-02802 Final9/24/20199/27/20199/27/2019 9:53:51 AMAFAIL
Builder Contact: Jason ###-####
HVAC Contact: Daniel ###-####
Access Instructions: On the far left house, on the backside of a pillar on the front porch, there’s a lockbox (9165), There are three keys inside; green goes to the middle house, the bare keys work on other two. Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- need duct blast report onsite
MEC19-04185 Final9/23/20199/27/20199/27/2019 9:14:45 AMAPASS
Homeowner Carrie Randel ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC18-02743 Mec-Aging Inspection9/27/20199/27/20199/27/2019 8:00:51 AM PASS
Doc Permit Expired ok permit not active
MEC18-02743 DOC - Permit Expired9/27/20199/27/20199/27/2019 7:59:04 AMAPASS
No calls or attempts to schedule inspection. Permit has not been active since 12-11-18 when it failed a R/I inspection. Doc Permit Expired ok