Inspections for the day of: Friday, September 7, 2018.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03089 Final9/5/20189/7/20189/7/2018 4:17:46 PMPFAIL
PLease call Michael 30 min prior to arrival. Cell phone also ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- line set penetration needs sealed- need to installed a wet switch on secoundary drain it cant be tied into the condensate pump
MEC18-04365 Final9/6/20189/7/20189/7/2018 4:03:20 PMPPASS
Please inspect in the early PM and call Rob when on way at ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- furnace co ok
MEC18-04365 Pressure Test9/6/20189/7/20189/7/2018 4:02:16 PMPPASS
Please inspect in the early PM and call Rob when on way at ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
20lb gas pressure test ok
MEC17-02895 Final9/6/20189/7/20189/7/2018 3:45:33 PMPFAIL
Shop Strange - Final at the request of Jack to close out job - call Sean with questions ###-#### Phone #: ###-#### Inspection requested via web by Bailey Esposito- b vent needs 1" clearances to combustibles- need you to meet me onsite for access to roof
MEC18-01029 Final9/6/20189/7/20189/7/2018 3:44:38 PMPFAIL
Please call Monica 30 min prior to arrival Phone #: ###-#### Inspection requested via web by Andrea Grigsby- need to see a 5lb flue test- also need to remove rubber coupler on flue vent and glue with sch 40 pvc- homeowner needs to add a/c disconnect to elecical permit- and need to see co detectors installed near bedrooms
MEC18-04366 Final9/6/20189/7/20189/7/2018 3:11:35 PMPNR
Please call Dave when on way at ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC18-04377 DOC - Permit Finaled9/7/20189/7/20189/7/2018 2:22:35 PMPPASS
final ok
MEC18-04377 Rough-in9/6/20189/7/20189/7/2018 2:21:56 PMPPASS
Please call Blake when on way at ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- R/I ok
MEC18-04080 Final8/31/20189/7/20189/7/2018 2:08:54 PMPNR
field Super; Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney- not ready still working on job- need to add gas piping to permit- need to also add duct work other to permit- plumbing contractor also needs to pull a permit for moving and replacing water heater
MEC18-04080 Pressure Test9/7/20189/7/20189/7/2018 2:05:51 PMPPASS
gas pressure test for moving gas line
-20lb gas pressure test ok
MEC18-04303 Pressure Test8/31/20189/7/20189/7/2018 1:41:30 PMPNR
INSTALLER ANAS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- no work has been done yet
MEC18-03664 Pressure Test9/7/20189/7/20189/7/2018 1:27:20 PMPPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige-60lb gas pressure test ok- tagged meter- needed another test because gas was being switched to high pressure
MEC17-04035 Final9/7/20189/7/20189/7/2018 1:23:07 PMPPASS
5lb flue pressure test- flue test ok- furnace ac coil ok
MEC18-04055 DOC - Permit Finaled9/7/20189/7/20189/7/2018 1:05:43 PMPPASS
fireplace final ok
MEC18-04055 Pressure Test9/6/20189/7/20189/7/2018 1:05:11 PMPPASS
BRUCE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza
- 20lb gas pressure test ok- tagged meter bar
MEC18-03786 Final9/6/20189/7/20189/7/2018 12:08:06 PMANH
Mr Lee Walton (owner) will be there. Phone #: ###-#### Inspection requested via web by Baldomero Guzman-no answered the door again
MEC18-04356 Rough-in9/6/20189/7/20189/7/2018 12:06:47 PMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace R/I ok
MEC18-01856 Final9/6/20189/7/20189/7/2018 10:33:57 AMAPASS
IF QUESTIONS CALL LYNN @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- condensate runs for cooling equipment ok
MEC18-04384 Rough-in9/7/20189/7/20189/7/2018 10:00:23 AMAFAIL
can you call about a half hour before heading over? Somebody should be there. But, just in case...

Nat
###-#### Phone #: ###-#### Inspection requested via web by Nat Golden
- range hood vent ok- need to see make up air for the range hood ducted outside of the return air for the furnace- also need to make sure there is access for the make up damper in the attic- need to see nail plates on relocated supply duct in the wall
MEC17-04330 Final9/6/20189/7/20189/7/2018 9:00:24 AMAFAIL
Please call technician 30 minutes ahead of arriving onsite. ###-####. Phone #: ###-#### Inspection requested via web by Melissa Skinner- one rtu needs 50 amp fuses in disconnect- one rtu needs gas line supported
- two rtu's in the center of the building have plumbing vents within 10' of the economizer
MEC17-04391 DOC - Permit Finaled9/7/20189/7/20189/7/2018 8:05:46 AMPPASS
final ok
MEC17-04391 Mec-Aging Inspection9/7/20189/7/20189/7/2018 8:05:15 AM PASS