FIR19-00126
| INSP-Sprinkler Rough-in | 5/7/2019 | 5/8/2019 | 5/8/2019 12:00:00 AM | A | PART |
|
|
***OK to cover the pipe chase. Heads added on both side of the spiral duct as requested. Still waiting on heads to be installed in stairwell ceilings.**MAS**
Contact Ken Orahood ###-#### 30 min prior to RTC insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank
|
FIR18-00673
| INSP-Final Inspection | 5/8/2019 | 5/8/2019 | 5/8/2019 12:00:00 AM | A | FAIL |
|
|
Escustechons missing or sprinklers low in rooms 109, 310, 120, 119, 110, 111. Tested interconnect with fire alarm panel-reports correctly. Forward flush is at 783 gallons.
Please call when in route Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
|