BLD18-04335
| FIRE-Final Inspection | 4/29/2019 | 4/30/2019 | 4/30/2019 2:21:46 PM | P | PART |
|
|
Per Ron Johnson 30 day temp approved. There is one upright head in east stairwell in basement that is up against the deck. This is area they didn't work in but will fix. OK for fire final.
AJ Phone #: ###-####
|
FIR19-00096
| INSP-Final Inspection | 4/30/2019 | 4/30/2019 | 4/30/2019 2:07:23 PM | P | FAIL |
|
|
No escutcheons installed in kitchen or office. Jerimiah is going to install today.
If i am needed please give me a heads up. Thanks. Jeremiah Robison Phone #: ###-#### Inspection requested via web by jeremiah robison
|
BLD18-04004
| FIRE-Final Inspection | 4/30/2019 | 4/30/2019 | 4/30/2019 2:06:10 PM | P | FAIL |
|
|
Fire extinguishers are not installed will need to be on reinspection. Pocket door was noted and will be reviewed by building inspector.
Nicol Phone #: ###-####
|
FIR19-00184
| INSP-Final Inspection | 4/30/2019 | 4/30/2019 | 4/30/2019 2:05:18 PM | P | FAIL |
|
|
Checked strobe placement and settings. When testing fire alarm the speaker circuit did not activate. Mike with State was going to verify programming and reschedule.
Call prior to going Phone #: 2089853303 >> Inspection requested via mobile web by Mike Kroll
|
NAF18-00110
| INSP-Final | 4/30/2019 | 4/30/2019 | 4/30/2019 12:03:50 PM | P | PART |
|
|
Approved for TCO 15 days. Extinguishers and exit lighting/emergency lighting fully functional. Bruce will change door hardware for office and get tag for extinguisher in office. DBS is not requiring paint booth sliding door to be fire rated or self closing.
Call prior to going Phone #: 2086065557 >> Inspection requested via mobile web by Bruce
|
NAF18-00144
| INSP-Final | 4/26/2019 | 4/30/2019 | 4/30/2019 10:59:02 AM | A | PASS |
|
|
Verified signals. Tested radio, smoke/pull, sprinkler monitor points. Passed final.
Phone #: 2085591551 >> Inspection requested via mobile web by Mike
|
NAF18-00140
| INSP-Final | 4/26/2019 | 4/30/2019 | 4/30/2019 10:58:12 AM | A | PASS |
|
|
Passed sprinkler final. Performed foward flush. Flow activated in 30 seconds.
We would like to perform this inspection in conjunction with fire alarm testing. Please call Rick with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00299
| INSP-Final Inspection | 4/29/2019 | 4/30/2019 | 4/30/2019 9:02:20 AM | A | PASS |
|
|
Conducted fire sprinkler final. Passed inspection.
Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00299
| INSP-Sprinkler Rough-in | 4/29/2019 | 4/30/2019 | 4/30/2019 9:01:29 AM | A | PASS |
|
|
Passed rough in.
Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
|
BLD19-00664
| FIRE-Final Inspection | 4/29/2019 | 4/30/2019 | 4/30/2019 12:00:00 AM | A | CANC |
|
|
Wrong permit called in. Fire safeing, not life safety. Cancelled.
Tom Phone #: ###-####
|