Inspections for the day of: Wednesday, May 8, 2019.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Scharfen
TitleFIRE CODE PLAN EXAMINER
Phone #208-608-7110
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00690 INSP-Final Inspection5/7/20195/8/20195/8/2019 12:00:00 AMAFAIL
Checked candella and smoke placment. Tested sprinkler interconnect and cell monitoring. While testing C wing found several problems:

Sounder bases in room will not resound alarms.
Room 309 bedroom strobe failed.
no ac labels on fire or nac panels.
Cell Dact needs to be added to fire alarm drawing and submitted as an as-build.
access control doors do not drop on fire alarm.

Did not verify horn strobe functionality in rest of building.

Still need to test majority of smoke detectors, CO detectors, access control interface, majority of notification devices.

Please call when in route. We are finalling sprinkler and FA at the same time. Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
BLD18-01629 FIRE-Final Inspection5/7/20195/8/20195/8/2019 12:00:00 AMACANC
Laren Phone #: ###-#### cancel per larren