FIR19-00588
| INSP-Final Inspection | 8/15/2019 | 8/16/2019 | 8/16/2019 4:14:38 PM | P | PASS |
|
|
Verified NAC panel supervision, tested synchronization. Fully funcional.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR19-00378
| INSP-Final Inspection | 8/16/2019 | 8/16/2019 | 8/16/2019 2:53:29 PM | P | PASS |
|
|
Tested and verified smokes/pulls and duct detectors. All speaker strobes functioned correctly. There is no hood installed in kitchen so point will need to be deleted off print and sent in as as build.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00461
| INSP-Final Inspection | 8/16/2019 | 8/16/2019 | 8/16/2019 1:45:30 PM | P | FAIL |
|
|
CO/Supervisory monitoring is not tied into AES, has not been pretested. Had conversation with technician. Will need to be scheduled after system has been properrly pretested.
end of day inspection if possible. please call ahead to coordinate. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD18-04283
| FIRE-Final Inspection | 8/15/2019 | 8/16/2019 | 8/16/2019 1:43:59 PM | P | FAIL |
|
|
Fire alarm not called in. Will need to schedule once fa is signed off
Marvin Phone #: ###-####
|
BLD19-01705
| FIRE-Final Inspection | 8/15/2019 | 8/16/2019 | 8/16/2019 1:42:45 PM | A | FAIL |
|
|
plans not on site. Contractor did not return call.
Phone #: ###-#### Inspection requested via web by Dustin Keyes
|
FIR19-00400
| INSP-Final Inspection | 8/16/2019 | 8/16/2019 | 8/16/2019 1:41:52 PM | P | PASS |
|
|
We would like to perform this in conjunction with fire life safety for BLD. Please call Jeff with questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD19-00228
| FIRE-Final Inspection | 8/15/2019 | 8/16/2019 | 8/16/2019 11:43:27 AM | A | PART |
|
|
Emergency discharge light not working. All e-lights inside functioned correctly. Extinguisher hung. No doors are hung. Will verify discharge either at fire alarm test or when building final is rescheduled.
Phone #: ###-#### Inspection requested via web by Russell Valline
|
BLD19-02644
| FIRE-Final Inspection | 8/15/2019 | 8/16/2019 | 8/16/2019 10:46:20 AM | A | PASS |
|
|
Jason Phone #: ###-####
|
FIR19-00484
| INSP-Final Inspection | 8/14/2019 | 8/16/2019 | 8/16/2019 10:33:07 AM | P | PART |
|
|
NETCON good. Verified signals. Passed pending asbuilt showing AES trouble connection to Zone 10 on FACP,
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|