Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00756 INSP-Final Inspection8/9/20198/9/20198/9/2019 1:56:32 PMPFAIL
Tested panel functions. AES is at NETCON 0 per Alarmco CS. Tested trouble and alarm signal. Speaker in FACP room is horn, needs to be a speaker. Outside speaker strobe by bell needs to be a strobe only. No lift on site. AES zone wire is not shielded. Unable to verify gym devices.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00564 INSP-Final Inspection8/6/20198/9/20198/9/2019 10:58:09 AMAPASS
verified signals, passed test.

This final is for a new Starlink Cellular Dialer. Phone #: ###-#### Inspection requested via web by Jason Heath
FIR17-00400 INSP-Final Inspection8/8/20198/9/20198/9/2019 10:05:47 AMAFAIL
No stamped prints on site. 3 troubles on fire alarm panel. 1-Missing SLC card (attic devices). 1 dirty smoke and 1 NAC battery troulbe. Told school that troubles will need to be clear and stamped prints on site for next test.

The fire doors in the main hallway for A, B, C wing, and cafeteria are repaired and latch closed when released from magnetic door holder. The Auditorium concession roll up door is now repaired. This should apply to FIR13-00187 as well, FIR17-00400 was pulled to address FIR13-00187 for some reason. Phone #: ###-#### Inspection requested via web by Jeff Gooch
FIR18-00348 INSP-Alarm Testing8/7/20198/9/20198/9/2019 9:42:18 AMAPASS
Verified Netcon, wiring, radio troulbe, restore,
alarm, trouble and supervisory from facp. Passed test.

Please meet Alarmco staff on site. Phone #: ###-#### Inspection requested via web by Jeff Gooch
FIR18-00184 INSP-Alarm Testing8/7/20198/9/20198/9/2019 9:06:56 AMAPASS
Tested AES panel. Netcon good. Radio supervised. Verified signals. Passed inpection.

Please meet Alarmco staff on site Phone #: ###-#### Inspection requested via web by Jeff Gooch
BLD19-00142 FIRE-Final Inspection8/8/20198/9/20198/8/2019 12:00:00 AMPNR
JCI unable to be on site till 8/9/2019-Afternoon to sound off horn strobes to make sure audibility noticed on last inspection has been repaired. Rescheduled.

Doug Phone #: ###-####