FIR18-00756
| INSP-Final Inspection | 8/9/2019 | 8/9/2019 | 8/9/2019 1:56:32 PM | P | FAIL |
|
|
Tested panel functions. AES is at NETCON 0 per Alarmco CS. Tested trouble and alarm signal. Speaker in FACP room is horn, needs to be a speaker. Outside speaker strobe by bell needs to be a strobe only. No lift on site. AES zone wire is not shielded. Unable to verify gym devices.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00564
| INSP-Final Inspection | 8/6/2019 | 8/9/2019 | 8/9/2019 10:58:09 AM | A | PASS |
|
|
verified signals, passed test.
This final is for a new Starlink Cellular Dialer. Phone #: ###-#### Inspection requested via web by Jason Heath
|
FIR17-00400
| INSP-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 10:05:47 AM | A | FAIL |
|
|
No stamped prints on site. 3 troubles on fire alarm panel. 1-Missing SLC card (attic devices). 1 dirty smoke and 1 NAC battery troulbe. Told school that troubles will need to be clear and stamped prints on site for next test.
The fire doors in the main hallway for A, B, C wing, and cafeteria are repaired and latch closed when released from magnetic door holder. The Auditorium concession roll up door is now repaired. This should apply to FIR13-00187 as well, FIR17-00400 was pulled to address FIR13-00187 for some reason. Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
FIR18-00348
| INSP-Alarm Testing | 8/7/2019 | 8/9/2019 | 8/9/2019 9:42:18 AM | A | PASS |
|
|
Verified Netcon, wiring, radio troulbe, restore, alarm, trouble and supervisory from facp. Passed test.
Please meet Alarmco staff on site. Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
FIR18-00184
| INSP-Alarm Testing | 8/7/2019 | 8/9/2019 | 8/9/2019 9:06:56 AM | A | PASS |
|
|
Tested AES panel. Netcon good. Radio supervised. Verified signals. Passed inpection.
Please meet Alarmco staff on site Phone #: ###-#### Inspection requested via web by Jeff Gooch
|
BLD19-00142
| FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/8/2019 12:00:00 AM | P | NR |
|
|
JCI unable to be on site till 8/9/2019-Afternoon to sound off horn strobes to make sure audibility noticed on last inspection has been repaired. Rescheduled.
Doug Phone #: ###-####
|