BLD-Final | 4/30/2013 | 4/30/2013 | 5/1/2013 | P | PASS |
Tony Young
|
|
|
Kana Tyler Phone #: ###-####
|
FIRE-Final Inspection | 4/29/2013 | 4/30/2013 | 4/30/2013 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 4/25/2013 | 4/29/2013 | 4/29/2013 | P | CANC |
Troy Cobbley
|
|
|
Hood suppression system is not ready yet. To be rescheduled. kana Phone #: ###-####
|
FIRE-Final Inspection | 4/22/2013 | 4/25/2013 | 4/25/2013 | P | FAIL |
Troy Cobbley
|
|
|
The hood suppression system is going to take so work to make code compliant per the contractor. When this work is complete the life safety can be finaled.
|
FIRE-Final Inspection | 4/18/2013 | 4/19/2013 | 4/19/2013 | A | FAIL |
Troy Cobbley
|
|
|
Repair the exit sign at the rear exit, provide exit sign at the front exit, provide emergency lighting in the Dining area, provide sticker at the main exit, provide re-certification/annual inspection for the hood suppression system, provide one 2a,10bc fire extinguisher and a K class for the kitchen, provide occupant load sign for "67" at the main exit in the Dining room.
|