Permit Information
Permit NumberBLD15-04184
StatusFinaled
Name ANDERSEN CONSTRUCTION CO
Site Address 611 S 8TH ST
Project NameThe Afton Condominiums
Customer Number 
ePlanReviewYes
Description
(THE AFTON CONDOMINIUMS – PHASE I DWELLING UNITS) (DRH14-00262) (11-15-16 PLAN MODIFICATION TO INSTALL A SEWAGE EJECTOR PUMP SINCE THE EXISTING SEWER LINE IS TOO HIGH FOR GRAVITY DRAINAGE. TO INSTALL A 3-HR FIRE DAMPER IN A FIRE RATED EXTERIOR FIRE WALL IN LIEU OF A FIRE/SMOKE DAMPER.) (10-20-16 PLAN MODIFICATION TO RELOCATE THE REQUIRED TYPE A DWELLING UNIT FROM THE 3RD STORY TO THE 1ST STORY. UNIT 112 WILL BE REVISED TO COMPLY AS A TYPE A DWELLING UNIT. UNIT 304 WILL COMPLY AS A TYPE B DWELLING UNIT INSTEAD OF COMPLYING AS A TYPE A DWELLING UNIT. ALL RECREATIONAL FACILITIES AND AMENITIES AVAILABLE TO THE OCCUPANTS OF THE UPPER DWELLING UNITS ARE REQUIRED TO BE AVAILABLE TO THE OCCUPANTS OF THE 1ST STORY DWELLING UNITS. THE RESIDENTIAL LOBBY WILL ALSO BE REVISED TO ELIMINATE A SMALL STORAGE ROOM AND TO RELOCATE THE MAIL AREA.) The fire sprinkler system (NFPA 13 below, next to, and above the podium per the “Special Design Standards for Type V Construction” ordinance) will be used for story and height increase. Grading was done under permit GRD15-00067. Phase I (two story concrete podium shell) was constructed under permit BLD15-03329. To construct a 3 story Type V-A apartment building having 3 one story dwelling units and 3 two story dwelling units next to the Type I-A podium building (about 2,533 square feet per story or 7,600 square feet for the building). To construct a 4 story Type V-A apartment building on top of the Type I-A podium building. Each story will have a floor area of about 9,545 square feet (38,180 square feet for the building). A common assembly area, one sleeping unit, and 4 one story dwelling units will be provided on the podium level. Five one story dwelling units will be provided on the 4th, 5th, and 6th stories each (15 total). Work is to include interior and exterior 1-hr fire-resistance-rated wood bearing walls, interior 1-hr fire-resistance-rated wood dwelling unit separation walls, 1-hr fire-resistance-rated wood floor-ceiling and roof-ceiling assemblies, a 2-hr fire-resistance-rated fire barrier wall above the 3-hr podium to function as a horizontal exit, interior nonbearing wood walls, interior doors, exterior doors and windows, exterior wall finishes, open egress balconies, a 1-hr fire-resistance-rated corridor, a 2-hr fire-resistance-rated elevator shaft, an elevator, two full height 2-hr fire-resistance-rated stairway exit enclosures with one extending to and serving the roof, millwork, restrooms, and interior finishes. All dwelling units are required to comply as Type B dwelling units, with at least one also complying as a Type A dwelling unit. The sleeping unit is required to comply as an accessible unit. To create storage areas, three two story live/work units, a two story lobby to serve the upper apartments, a shell retail sales tenant space with a high ceiling, and a two story enclosed parking garage within the Type I-A podium building on the 1st and 2nd stories. Work is to include stairways to serve 2nd stories, 1-hr fire-resistance-rated non-combustible dwelling unit separation walls, interior noncombustible walls, restrooms, interior doors, exterior doors and windows, exterior wall finishes, millwork, and interior finishes. Special Inspection is required for structural steel, welding, structural wood panel shear walls, wood floor and roof diaphragms, and masonry. Structural Observation by the Engineer of Record is required. Deferred submittal items include engineered wood trusses. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/8/20179/8/20179/8/2017PPASS
DetailsDave Hannah
for perm occ
FIRE-Final Inspection9/7/20179/7/20179/7/2017APASS
DetailsJim Page
Fire sprinkler inspections complete, fire alarm inspections complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD-Final9/5/20179/6/20179/7/2017PPART
DetailsDave Hannah
until 203// Amy Phone #: ###-#### ok for temp occ
BLD-Aging Inspection8/25/20178/25/20178/31/2017 PEND
DetailsDave Hannah
BLD-Final8/31/20178/31/20178/31/2017PPART
DetailsDave Hannah
Jason Phone #: ###-#### 201and 202 ok for temp occ
BLD-Final6/16/20176/19/20176/19/2017APEND
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Final6/15/20176/16/20176/16/2017PPART
DetailsDave Hannah
Amy Phone #: ###-#### ok for temp occ needs to finish units 111 12 113 and 211 12 213
FIRE-Final Inspection6/16/20176/16/20176/16/2017PPART
DetailsJim Page
Life fire safety inspection complete for TCO requested area's (Main builing, living area's for live/work units, parking levels 1 and 2, lobby area's for levels 1 and 2 condo units and common area's for levels 3, 4, 5 and 6. Townhomes are not part of the TCO, townhome life fire safety inspection to be completed at a later date). Fire alarm inspection complete for TCO area's (monitoring verified, monitoring to be active at end of business day 16JUNE2017, all occupied TCO area's to be actively monitored at end of work day after 16JUNE2017, fire alarm system cannot be placed out of servicefor more than work day hours) fire sprinkler inspection complete for TCO area's, active fire sprinkler protection for entire building to include townhomes, fire extinguishers in place with current inspection tags for TCO area's, knox box is in place by main entry on river street side of building.
BLD-Conference6/15/20176/16/20176/16/2017APASS
DetailsDave Hannah
Amy Phone #: ###-####
BLD-Other6/5/20176/6/20176/6/2017ADONE
DetailsDave Hannah
Review documentation from MTI Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Other6/1/20176/2/20176/2/2017PDONE
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Conference5/31/20176/1/20176/1/2017APASS
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Energy code compliance5/12/20175/15/20175/15/2017APASS
DetailsDave Hannah
Garden Shed on 3rd Floor Patio Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Conference4/11/20174/12/20174/12/2017ACANC
DetailsJim Storey
Phone #: ###-#### >> Inspection requested via web by Ami Tracy Inspection cancelled from web by: Ami Tracy
BLD-Energy code compliance3/8/20173/9/20173/9/2017APASS
DetailsDave Hannah
6th Floor Fire Proofing Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Energy code compliance3/2/20173/3/20173/3/2017ACANC
DetailsDave Hannah
6th Floor Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Energy code compliance2/16/20172/17/20172/17/2017APART
DetailsJim Sly
First floor town homes Phone #: ###-#### Inspection requested via web by Ami Tracy
Units 111, 112, 113.
BLD-Framing/Rough-in1/18/20171/19/20171/20/2017APART
DetailsDave Hannah
Level 2 Framing Phone #: ###-#### Inspection requested via web by Ami Tracy ok to one side last two areas
BLD-Energy code compliance1/10/20171/11/20171/11/2017APASS
DetailsDave Hannah
Elevator Insulation Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Framing/Rough-in12/16/201612/19/201612/19/2016APASS
DetailsDave Hannah
5th Floor framing Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Wall cover12/16/201612/16/201612/16/2016PDEFR
DetailsJim Storey
5th Floor Insulation Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Conference12/5/201612/6/201612/6/2016APART
DetailsDave Hannah
6th Floor Framing Phone #: ###-#### Inspection requested via web by Ami Tracy ok to insulate
BLD-Framing/Rough-in11/22/201611/28/201611/28/2016APASS
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Ami Tracy
BLD-Framing/Rough-in11/21/201611/22/201611/22/2016APASS
DetailsDave Hannah
Framing Inspection Phone #: ###-#### Inspection requested via web by Ami Tracy first second floors ok to one side int walls and cover ext walls 4orth floor ok to cover walls
BLD-Framing/Rough-in11/16/201611/17/201611/21/2016APASS
DetailsDave Hannah
Level 4 Insulation Phone #: ###-#### Inspection requested via web by Ami Tracy