Permit Information
Permit NumberBLD17-03618
StatusIssued
Name ESI
Site Address 6280 N EAGLE RD
Project NameTarget Store #1230
Customer Number 
ePlanReviewYes
Description
(TARGET STORE #1230) **Permit for tenant improvements to an existing Target store. Work to include new site amenities; new exterior entry facade and roof framing; new restroom, dressing room, office, front sales configuration; new non-bearing interior partition walls; new doors; new plumbing, mechanical, and electrical; and new interior finishes in compliance with Ch. 8 of the 2012 IBC. A certificate of completion is to be issued upon completion and approval of the project. Special Inspections required per attached Form 310. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JAR**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/9/20184/11/20184/11/2018PNR
DetailsJim Sly
Curtis Phone #: ###-####
Need Electr. and Fire Finals.
FIRE-Final Inspection4/9/20184/11/20184/11/2018AFAIL
DetailsTroy Cobbley
Todays inspection was just to meet/provide a correction notice for the existing deficient fire alarm system. It appears that the owner is going to move in the direction of an upgrade agreement. I discussed with Curtis the need to final all of the fire sprinkler permits, and go through the life safety items such as the emergency lights, exit signs....ect.


Curtis Phone #: ###-####
BLD-Ceiling Grid Inspection3/20/20183/21/20183/21/2018APASS
DetailsJim Sly
Curtis Phone #: ###-####
BLD-Ceiling Grid Inspection3/1/20183/2/20183/2/2018APART
DetailsJim Sly
Chris Phone #: ###-####
Select rooms.
BLD-Framing/Rough-in3/1/20183/2/20183/2/2018APART
DetailsJim Sly
Chris Phone #: ###-####
Select walls......OK.
FIRE-Final Inspection2/27/20182/28/20182/28/2018PFAIL
DetailsTroy Cobbley
Inspection was actually a conference. I noted that the electrical engineer shows two strobes in remodeled rooms but there is no notification elsewhere in the store. Plans may need modified to delete these devices. I noted that a FIR permit will be requierd for the two new duct smoke detectors for units 10 and 12. I will need emergency lighting provided in the pass of egress from the remodeled areas and all existing emergency fixtures functional. There is still one fire sprinkler permit for phase 1 that has not been finaled yet.

Chris Phone #: ###-####
BLD-Ceiling Grid Inspection2/20/20182/20/20182/21/2018PPASS
DetailsJim Sly
Curtis Phone #: ###-####
BLD-Framing/Rough-in2/2/20182/2/20182/2/2018PPART
DetailsJim Sly
Curtis Phone #: ###-####
BLD-Ceiling Grid Inspection1/22/20181/22/20181/23/2018PPASS
DetailsJim Sly
Curtis-partial Phone #: ###-####
BLD-Framing/Rough-in1/9/20181/10/20181/10/2018APART
DetailsJim Sly
Curtis Phone #: ###-####