BLD-Aging Inspection | 6/27/2019 | 6/27/2019 | 6/27/2019 | | DONE |
Tell Riley
|
|
|
Final passed
|
BLD-Aging Inspection | 6/26/2019 | 6/26/2019 | 6/26/2019 | | DONE |
Tell Riley
|
|
|
final passed//see below// BLD-Final 2/11/2019 2/11/2019 2/12/2019 P PASS DetailsJim Sly
|
BLD-Final | 2/11/2019 | 2/11/2019 | 2/12/2019 | P | PASS |
Jim Sly
|
|
|
|
BLD-Aging Inspection | 2/8/2019 | 2/8/2019 | 2/11/2019 | | CANC |
Jim Sly
|
|
|
|
BLD-Final | 9/25/2018 | 9/26/2018 | 9/26/2018 | A | PASS |
Jim Sly
|
|
|
Phone #: ###-#### Inspection requested via web by Kenny Elumbaugh OK for Perm Occ.
|
FIRE-Final Inspection | 9/25/2018 | 9/26/2018 | 9/26/2018 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed, the lock was blanked off at the beer cooler, two CO detectors have been installed and Bob Tikker provided letter to delete the two duct smoke detectors.
Phone #: ###-#### Inspection requested via web by Kenny Elumbaugh
|
BLD-Final | 9/25/2018 | 9/25/2018 | 9/25/2018 | P | NR |
Jim Storey
|
|
|
Please late as possible. Thank you Phone #: ###-#### Inspection requested via web by Kenny Elumbaugh fire failed
|
FIRE-Final Inspection | 9/24/2018 | 9/25/2018 | 9/25/2018 | A | FAIL |
Troy Cobbley
|
|
|
Provide single action ADA hardware for the beer cooler, provide the duct smoke detectors per the approved drawings or get engineer approval to delete since the units are only 1600cfm, provide the CO ventilation and detection system as per review note #11
Phone #: ###-#### Inspection requested via web by Kenny Elumbaugh
|
FIRE-Final Inspection | 9/20/2018 | 9/24/2018 | 9/24/2018 | A | FAIL |
Troy Cobbley
|
|
|
Missing the first two sheets of the drawings, missing small documents, missing sticker at door, fire extinguishers expired, need ADA complicant hardware on beer cave and restroom doors....ect.
Morgan Phone #: ###-####
|
BLD-Framing/Rough-in | 8/16/2018 | 8/17/2018 | 8/17/2018 | P | PASS |
Jim Sly
|
|
|
Morgan Phone #: ###-####
|
BLD-Wall Bracing | 8/7/2018 | 8/7/2018 | 8/8/2018 | P | PASS |
Jim Sly
|
|
|
Morgan Phone #: ###-####
|