BLD-Final | 6/5/2019 | 6/6/2019 | 6/6/2019 | A | PASS |
Dave Hannah
|
|
|
after 10 // Larren Phone #: ###-####
|
FIRE-Final Inspection | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected. Sprinkler work is complete, access control interface with fire alarm system complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
Larren Phone #: ###-####
|
FIRE-Final Inspection | 5/7/2019 | 5/8/2019 | 5/8/2019 | A | CANC |
Mark Scharfen
|
|
|
Laren Phone #: ###-#### cancel per larren
|
FIRE-Final Inspection | 5/7/2019 | 5/8/2019 | 5/7/2019 | A | CANC |
Troy Cobbley
|
|
|
Larren Phone #: ###-####-as per Larin-cance inspection
|
FIRE-Final Inspection | 4/2/2019 | 4/3/2019 | 4/3/2019 | A | FAIL |
Jim Page
|
|
|
Access control for north gym door did not release on general fire alarm.
Lauren Phone #: ###-####
|
FIRE-Final Inspection | 3/26/2019 | 3/27/2019 | 3/27/2019 | A | FAIL |
Jim Page
|
|
|
Access control did not release on general alram.
Larren Phone #: ###-####
|
FIRE-Final Inspection | 3/25/2019 | 3/25/2019 | 3/25/2019 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact. Need FIR permits for fire alarm and fire sprinkler work per notes entered on 12FEB 2019.
Laurin Phone #: ###-####
|
BLD-Final | 2/12/2019 | 2/12/2019 | 2/12/2019 | A | NR |
Dave Hannah
|
|
|
needs fire finals
|
BLD-Conference | 2/11/2019 | 2/11/2019 | 2/12/2019 | P | DONE |
Dave Hannah
|
|
|
Laren Phone #: ###-####
|
FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 | A | FAIL |
Jim Page
|
|
|
Access control door leading to space needs to comply with section 1010.1.9.8 of the 2015 IFC. Fire sprinkler head in space located by office is overspaced, fire sprinkler head needs to be added to be code compliant.
Larren Phone #: ###-####
|