Permit NumberBLD18-01629
StatusFinaled
Name EIGHTH & MAIN CONDOMINIUM ASSOCIATI
Site Address 800 W MAIN ST Unit: 210
Project NameK-Cycling at the Gym Suite 210
Customer Number 
ePlanReviewYes
Description
(K-CYCLING AT THE GYM - 8TH & MAIN - SUITE #210) Permit is to remodel an existing 2,728 sq. ft. business space. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select millwork, removal and relocation of select interior storefront window/door, new 64 sq. ft. platform, electrical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final6/5/20196/6/20196/6/2019APASS
DetailsDave Hannah
after 10 // Larren Phone #: ###-####
FIRE-Final Inspection6/3/20196/4/20196/4/2019APASS
DetailsJim Page
Previously noted items have been corrected. Sprinkler work is complete, access control interface with fire alarm system complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.

Larren Phone #: ###-####
FIRE-Final Inspection5/7/20195/8/20195/8/2019ACANC
DetailsMark Scharfen
Laren Phone #: ###-#### cancel per larren
FIRE-Final Inspection5/7/20195/8/20195/7/2019ACANC
DetailsTroy Cobbley
Larren Phone #: ###-####-as per Larin-cance inspection
FIRE-Final Inspection4/2/20194/3/20194/3/2019AFAIL
DetailsJim Page
Access control for north gym door did not release on general fire alarm.

Lauren Phone #: ###-####
FIRE-Final Inspection3/26/20193/27/20193/27/2019AFAIL
DetailsJim Page
Access control did not release on general alram.

Larren Phone #: ###-####
FIRE-Final Inspection3/25/20193/25/20193/25/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact. Need FIR permits for fire alarm and fire sprinkler work per notes entered on 12FEB 2019.

Laurin Phone #: ###-####
BLD-Final2/12/20192/12/20192/12/2019ANR
DetailsDave Hannah
needs fire finals
BLD-Conference2/11/20192/11/20192/12/2019PDONE
DetailsDave Hannah
Laren Phone #: ###-####
FIRE-Final Inspection2/11/20192/12/20192/12/2019AFAIL
DetailsJim Page
Access control door leading to space needs to comply with section 1010.1.9.8 of the 2015 IFC. Fire sprinkler head in space located by office is overspaced, fire sprinkler head needs to be added to be code compliant.

Larren Phone #: ###-####