BLD-Final | 6/17/2019 | 6/18/2019 | 6/18/2019 | A | PASS |
Jim Storey
|
|
|
Rachel Phone #: ###-#### final ok no card on site.
|
FIRE-Final Inspection | 6/17/2019 | 6/17/2019 | 6/17/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
|
BLD-Conference | 5/20/2019 | 5/21/2019 | 5/21/2019 | A | NR |
Jim Storey
|
|
|
Drew Phone #: ###-#### pending fire spk/exit lumation
|
FIRE-Final Inspection | 5/20/2019 | 5/20/2019 | 5/20/2019 | P | FAIL |
Jim Page
|
|
|
Provide fire sprinkler under east overhead door (Any modifications/additions to the fire sprinkler system requires a permit). Exit signs/emergency lights need to be serviced, lights did not stay illuminated when disconnected from AC power.
Drew-please call when on way Phone #: ###-####
|