Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberBLD20-00514
StatusIssued
Name SI CONSTRUCTION LLC
Site Address 6303 W TIERRA LN
Project NameLot 12 Unit C
Customer NumberBLD20-00514, BLD20-00516-00517
ePlanReviewYes
Description
(THREE PERMITS FILED UNDER BLD20-00514) Permit for the construction of a new 1661 sq. ft., 2 story (first story 1023 sq. ft., second story 638 sq. ft.) Townhouse with 3 bedrooms, 2.5 bathrooms, approximately 64 sq. ft. of covered patio/porch and a 520 sq. ft. attached garage per the approved plans and any notations. Rescheck Energy Compliance. R-2D zoning and setbacks per planning. ***RDP***
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Framing/Rough-in8/10/20208/11/20208/11/2020APASS
DetailsMike Jordan
Phone #: 2088703262 >> Inspection requested via mobile web by Lucas Eells. All framing issues corrected. ok to insulate.
BLD-Framing/Rough-in8/3/20208/4/20208/4/2020AFAIL
DetailsMike Jordan
Phone #: 2088703262 >> Inspection requested via mobile web by Lucas Eells. Fireblock at ceiling level 1st. an d2nd. floors between staggered stud 2hr. wall. Provide putty pads on back to back electrical boxes. Provide letter from engineer deleting straps. Remove all foam from top plates and firecaulk, also firecaulk penetrations. C/N posted.
BLD-Other6/18/20206/19/20206/19/2020APASS
DetailsMike Jordan
Phone #: 2088703262 >> Inspection requested via mobile web by Lucas Eells. 5/8 type x rock for fire walls at exterior locations and prerock areas.
BLD-Wall Bracing6/15/20206/16/20206/16/2020APASS
DetailsMike Jordan
Phone #: 2088703262 >> Inspection requested via mobile web by Lucas Eells. Exterior shear only ok. Also met with contractor to discuss firewall issues.
BLD-Wall Bracing6/10/20206/12/20206/12/2020APART
DetailsMike Jordan
Phone #: 2088703262 >> Inspection requested via mobile web by Lucas Eells. Needs to install all missed floor to floor straps, nail missed areas. Also noted issues with installed sheet rock for fire walls as well as continuity issues that need to be addressed prior to proceeding.
BLD-Foundation4/10/20204/13/20204/13/2020PPART
DetailsMike Jordan
Pat *left voicemail* Phone #: ###-####
BLD-Footing4/9/20204/10/20204/10/2020PPART
DetailsMike Jordan