Information based on query as of Thursday, April 18, 2024.
Permit Information
Permit NumberELE14-02862
StatusFinaled
Name STEPHENS ELECTRIC INC
Site Address 2418 N 21ST ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection2/7/20192/7/20192/12/2019 PASS
DetailsMark Moncarr
Existing home demolished, and new home constructed on parcel.
Final2/12/20192/12/20192/12/2019PPASS
DetailsMark Moncarr
Talked to Terry with Stephens Electric on 2/12/19. Drove to site and verified that house was demolished and a new home is now on property.
Permanent Service10/15/201410/15/201410/15/2014PFAIL
DetailsRock A. Hudson
ACCESS CODE 6500

Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 250.53(D)(1)(2)- Metal Underground Water Pipe. If used as a grounding electrode, metal underground water pipe shall meet the requirements of 250.53(D)(1) and (D)(2). (1) Continuity. Continuity of the grounding path or the bonding connection to interior piping shall not rely on water meters or filtering devices and similar equipment. (2) Supplemental Electrode Required. A metal underground water pipe shall be supplemented by an additional electrode of a type specified in 250.52(A)(2) through (A)(8). Clamp loose on poping system and con not verify additional rod wire is under deck