Information based on query as of Sunday, May 19, 2024.
Permit Information
Permit NumberELE15-00346
StatusFinaled
Name BENDER ELECTRIC SERVICES
Site Address 1205 N 11TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: remodel of 3rd level of existing home power and lighting
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/9/20156/9/20156/9/2015PPASS
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by kendall bender ok final
Electrical Rough-In2/27/20153/2/20153/2/2015APASS
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by kendall bender
Discusssed with contractor j box to right of tub in in attic space at floor level needing access prior to inspection. Verify access to this j box at final. picture on phone. RI ok to cover
Electrical Rough-In2/26/20152/26/20152/26/2015AFAIL
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by kendall bender
Called Mike
250.148 (C) Metal Boxes. A connection shall be made between the
one or more equipment grounding conductors and a metal
box by means of a grounding screw that shall be used for
no other purpose, equipment listed for grounding, or a
listed grounding device.
300.4(A) Cables and Raceways Through Wood Members.
(1) Bored Holes. In both exposed and concealed locations,
where a cable- or raceway-type wiring method is installed
through bored holes in joists, rafters, or wood members,
holes shall be bored so that the edge of the hole is not less
than 32 mm (11/4 in.) from the nearest edge of the wood
member. Where this distance cannot be maintained, the
cable or raceway shall be protected from penetration by
screws or nails by a steel plate(s) or bushing(s), at least
1.6 mm (1/16 in.) thick, and of appropriate length and width
installed to cover the area of the wiring.
314.29 Boxes, Conduit Bodies, and Handhole Enclosures
to Be Accessible. Boxes, conduit bodies, and handhole
enclosures shall be installed so that the wiring contained
in them can be rendered accessible without removing
any part of the building or structure or, in underground circuits,
without excavating sidewalks, paving, earth, or other
substance that is to be used to establish the finished grade.
Electrical Rough-In2/16/20152/17/20152/17/2015APASS
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by kendall bender
RI Floor cover OK thrid floor