Permit Information
Permit NumberELE17-01320
StatusFinaled
Name UNITED ELECTRIC CONTRACTING
Site Address 515 W IDAHO ST
Project Name 
Customer NumberOCHOS
ePlanReviewNo
Description
Alteration: New Panel K, New Circuits in Kitchen & Bar Areas, Wiring to Evaporator for Walk-In Cooler, Wiring and Installation of Lights, New Dimmers, OC Sensors, Demo, Misc Receps & Power, Relocate Existing Meter Center to West Exterior Wall
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/5/20186/7/20186/7/2018APASS
DetailsRock A. Hudson
Contact Tate Borstelman with any questions Phone #: ###-#### Inspection requested via web by JENNY EMEL Final ok
Electrical Rough-In10/16/201710/17/201710/17/2017APASS
DetailsRock A. Hudson
Requesting inspection for cover in the bar only

Contact Tate Borstelman with any questions or comments - he will be on site

Thank you and have a nice day!
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Area noted bar wall rough in ok cover
Electrical Rough-In6/7/20176/7/20176/7/2017PPASS
DetailsRock A. Hudson
CONTACT TATE BORSTELMAN WITH ANY QUESTONS OR CONCERNS -

INSPECTION IS FOR KITCHEN ONLY - READY TO COVER Phone #: ###-#### Inspection requested via web by JENNY EMEL
kitchen/ prep area only walls and hardlid rough in ok cover.
Electrical Rough-In5/23/20175/24/20175/24/2017APASS
DetailsEric Story
Requested Inspection is for Cover for Walk In Cooler

Contact is Tate Borstelman ###-####
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Walk in cooler in basement walls and ceiling only
ok cover
Permanent Service5/11/20175/11/20175/11/2017PPASS
DetailsRock A. Hudson
Re-Inspection of service panel moved from one location to another Phone #: ###-#### Inspection requested via web by JENNY EMEL
Main breaker B changed to 22k rating others to be changed Monday the15th as they are on order.
p/s u/g n ok
Permanent Service5/9/20175/10/20175/10/2017PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by JENNY EMEL
110.24- Available fault current shall be posted prior to permenant service inspection to verify main disconnect rated for current available at line terminals as per 110.9. 10k rated main breakers.
10,959 L-L...8,217 L-N. Next size shall be installed.
Electrical Rough-In5/3/20175/3/20175/3/2017PPASS
DetailsRock A. Hudson
THIS REQUEST IS FOR UNDERGROUND READY TO COVER

Please contact Tate with any questions or concerns @ ###-####

Thank you and have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Back area to be covered by an elevated deck creating 3' to 5' depth on underground. Rough in ok cover