Final | 5/13/2019 | 5/17/2019 | 5/16/2019 | A | PASS |
James Ady
|
|
|
Contact: Paul Wheeler.... old permit for consultation, need to final and close Phone #: ###-#### Inspection requested via web by Deb Gooden All items in conference have been addressed. Final ok
|
Final | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | CANC |
James Ady
|
|
|
Contact: Paul Wheeler Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|
Conference | 9/11/2017 | 9/12/2017 | 9/12/2017 | A | DONE |
James Ady
|
|
|
Contact: Brian Gee.. Would like to schedule for 9:00 or 11:00, please call before going Phone #: ###-#### Inspection requested via web by Deb Gooden Met onsite Discussed article 110.26 B. Electrical working space shall not be used for storage. 110.26 C 2. @ Egress paths for services over 1200Amps. 110.26 C 3. Panic hardware on egress doors on services over 800A. 110.26 D. Lighting for service rooms.210.64. Service Receptacle Required. Also discussed removing old exposed romex and "cleaning" up unsafe wiring.
|