Final | 1/17/2019 | 1/18/2019 | 1/17/2019 | A | PASS |
Rock A. Hudson
|
|
|
Please call Lynn at ###-#### prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor Final ok
|
Final | 1/16/2019 | 1/17/2019 | 1/17/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Please call Lynn at ###-#### prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor 110.26- Minimum work space shall be provided for HVAC disconnecting means near east offices. 210.8(B)- All 120 volt 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. Refrigerator in break room
|
Electrical Rough-In | 1/14/2019 | 1/15/2019 | 1/15/2019 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling grid inspection is needed. Please call Lynn at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor Grid rough in ok cover
|
Electrical Rough-In | 11/16/2018 | 11/19/2018 | 11/19/2018 | A | PASS |
Rock A. Hudson
|
|
|
Please call Lynn at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor Conference room 182 square ft, Enter thru 225 N 9th entrance for access to elevators. Wall rough in ok cover
|