Final | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Terry Scott.... corrections made...ok to final
|
Final | 1/7/2019 | 1/8/2019 | 1/8/2019 | A | FAIL |
Tom Saunders
|
|
|
For access please call Tom 1/2 hr prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Scott.. 1..open ground showing in grounded outlets thru out living rm...install gfi protection for outlets or non grounded outlets...406.4(D) 2..pantry outlets need GFI protection..210.8(A) & 210.52(C) 3..counter in nook/dining needs outlets serving countertop...210.52(C), 210.8(A),
|
Electrical Rough-In | 11/1/2018 | 11/1/2018 | 11/1/2018 | P | PASS |
Tom Saunders
|
|
|
For access please call Luke 1/2 hr prior to inspection.###-#### Phone #: ###-#### Inspection requested via web by Terry Scott
rough ok to cover...kitchen, laundry, and living room walls-excluding living room ceiling
|