Final | 10/22/2019 | 10/23/2019 | 10/23/2019 | A | PASS |
James Ady
|
|
|
Contact Brandon for finalizing any remaining open issues. (GFCI protection) Phone #: ###-#### Inspection requested via web by Tom Betty All items have been corrected final ok
|
Final | 10/21/2019 | 10/22/2019 | 10/22/2019 | A | PART |
James Ady
|
|
|
Contact Brandon for area B and the penthouse for final inspection. Phone #: ###-#### Inspection requested via web by Tom Betty 210.8 GFCI protection shall be installed in a readily accessible location.(GFCI breaker needed for Breakroom Ice machine and undercounter fridge.) GFCI has been installed in Decon. room. Partial final ok
|
Final | 10/17/2019 | 10/21/2019 | 10/21/2019 | A | PART |
James Ady
|
|
|
Contact Brandon for partial final of job. Basement and Area A final only. Phone #: ###-#### Inspection requested via web by Tom Betty Check for GFCI recep in Decon room to the right of sink. Make sure equipment has not been mounted infront of Decon sprayer Disc. Plumbing drain was stubbed but no equipment had been installed at time of inspection. Arrea "A" only (procedure rooms, Hall ways, restrooms and locker rooms) Basement "Fan room" and main electrical room ok partial final only ok
|
Electrical Rough-In | 10/15/2019 | 10/16/2019 | 10/16/2019 | P | PASS |
James Ady
|
|
|
Level 1 above ceiling corridor rough in needed. Phone #: ###-#### Inspection requested via web by Tom Betty Back corridor and Waiting area corridor Ceiling only ok to cover
|
Electrical Rough-In | 10/9/2019 | 10/14/2019 | 10/14/2019 | A | NR |
James Ady
|
|
|
Contact Cody for level 1 corridor above ceiling rough ins. Phone #: ###-#### Inspection requested via web by Tom Betty Not ready recall
|
Electrical Rough-In | 9/24/2019 | 9/26/2019 | 9/26/2019 | A | PASS |
James Ady
|
|
|
Contact Cody for level 1 restroom rough in. Phone #: ###-#### Inspection requested via web by Tom Betty Restroom only ok to cover
|
Electrical Rough-In | 9/12/2019 | 9/16/2019 | 9/16/2019 | A | PASS |
James Ady
|
|
|
Ceiling inspections of area A and B level 1. Phone #: ###-#### Inspection requested via web by Tom Betty Area A and B plus waiting room Drop ceiling only ok to cover
|
Electrical Rough-In | 9/9/2019 | 9/9/2019 | 9/9/2019 | A | PASS |
James Ady
|
|
|
Rough in raceways, boxes and cabling in occupied spaces on level 1. Contact Andrea at ###-#### or Brandon at ###-####. Phone #: ###-#### Inspection requested via web by Tom Betty Fire alarm only rough in ok
|
Electrical Rough-In | 8/22/2019 | 8/23/2019 | 8/23/2019 | A | PASS |
Rock A. Hudson
|
|
|
Level 1 corridor above ceiling by electrical room. Phone #: ###-#### Inspection requested via web by Tom Betty Corridor noted is temporary ceiling and will be replaced in future. Fire protection raceways present have existing fire circuits installed that will be removed when replaced with new system. Area noted grid rough in ok cover
|
Electrical Rough-In | 8/7/2019 | 8/8/2019 | 8/8/2019 | A | PASS |
James Ady
|
|
|
OR room ceiling access panels. Phone #: ###-#### Inspection requested via web by Tom Betty Access added Ceilings in OR 1,2 and 3 ok to cover
|
Electrical Rough-In | 8/2/2019 | 8/6/2019 | 8/6/2019 | A | PART |
James Ady
|
|
|
Above ceiling in 4 OR rooms. Phone #: ###-#### Inspection requested via web by Tom Betty Decon room and OR room 4 ok to cover. OR room 1,2,3 need access to copper gas line bonding connections.
|
Electrical Rough-In | 7/25/2019 | 7/26/2019 | 7/26/2019 | A | PASS |
James Ady
|
|
|
Basement electrical rooms normal power and emergency power panels and transformer. 1st floor electrical room panels and transformers. Phone #: ###-#### Inspection requested via web by Tom Betty Main Electrical room and Basement power panels ok.
|
Electrical Rough-In | 7/17/2019 | 7/19/2019 | 7/19/2019 | A | PASS |
James Ady
|
|
|
Contact Brandon for Area B corridors, restroom, waiting, reception area. Phone #: ###-#### Inspection requested via web by Tom Betty Area "C" as marked on 1st floor power plan. Walls only in Corridors, waiting, reception and restrooms ok to cover
|
Conference | 7/11/2019 | 7/12/2019 | 7/12/2019 | A | DONE |
James Ady
|
|
|
Disconnecting means of chillers with line side controller and load side VFD on opposite sides of units and out of site from VFD''s. Phone #: ###-#### Inspection requested via web by Tom Betty As long as Disc. is lockable, location ok.
|
Electrical Rough-In | 6/24/2019 | 6/25/2019 | 6/25/2019 | A | PASS |
James Ady
|
|
|
Hard lid rough-in inspection. Contact Jon Novak Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Hard lids in locked rooms only ok to cover
|
Rough-In Permanent Service | 6/13/2019 | 6/14/2019 | 6/14/2019 | A | PASS |
James Ady
|
|
|
Contact Jon Novak for new utility service rough in. Phone #: ###-#### Inspection requested via web by Tom Betty New gear in ll1 Mechanical room ok p/s u/g n ok
|
Electrical Rough-In | 6/11/2019 | 6/12/2019 | 6/12/2019 | A | PASS |
James Ady
|
|
|
Wall rough in area C level 1. Phone #: ###-#### Inspection requested via web by Tom Betty Area C only as marked on print walls only ok to cover
|
Electrical Rough-In | 6/6/2019 | 6/7/2019 | 6/7/2019 | P | PASS |
James Ady
|
|
|
Contact Jon Novak for area B 1st floor wall rough in. Phone #: ###-#### Inspection requested via web by Tom Betty Area B ok to cover as marked on print. Walls only
|
Electrical Rough-In | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | PASS |
Rock A. Hudson
|
|
|
Contact Toby Davis for level 1 4 operating rooms dough in. Phone #: ###-#### Inspection requested via web by Tom Betty 4 OR rooms wall rough in ok cover
|
Electrical Rough-In | 5/22/2019 | 5/23/2019 | 5/22/2019 | A | CANC |
Rock A. Hudson
|
|
|
Contact Jon Novak for rough in inspection of level1 4 operating rooms. Phone #: ###-#### >> Inspection requested via web by Tom Betty Inspection cancelled from web by: Tom Betty
|
Electrical Rough-In | 5/15/2019 | 5/16/2019 | 5/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
Wall Rough in inspection. Contact Jon Novak Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Area (A), except 4 operating rooms, wall rough in ok cover
|