Information based on query as of Wednesday, May 15, 2024.
Permit Information
Permit NumberELE19-00970
StatusFinaled
Name R M E INC
Site Address 325 W IDAHO ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install new service, mechanical connections, lights, outlets per plans for new St. Luke''s DCIP Center.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/4/20199/4/20199/4/2019PPASS
DetailsRock A. Hudson
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Area in question not a storage space, it is a crawl space, no luminaire required. Final ok
Final8/27/20198/28/20198/28/2019APART
DetailsJames Ady
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 210.70C Underfloor spaces used for storage shall have at least 1 lighting outlet. Patial final only ok
Electrical Rough-In8/5/20198/6/20198/6/2019APASS
DetailsRock A. Hudson
Basement ceiling cover. Buster is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Area noted rough in ok cover
Electrical Rough-In7/3/20197/3/20197/3/2019PPASS
DetailsJames Ady
Ceiling cover in area B. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Area B minus Stairs ceilings ok to cover
Electrical Rough-In7/1/20197/1/20197/1/2019PPASS
DetailsJames Ady
Ceiling cover. Phone #: ###-#### Inspection requested via web by Buster Bowen Area "A" minus back entry hall Ceiling only ok to cover
Permanent Service6/13/20196/14/20196/14/2019APASS
DetailsRock A. Hudson
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 85K rated main, available fault current will verify on future trip due to Idaho power has not released plans for new transformer and service entrance conductors at time of inspection.
p/s u/g n ok
Electrical Rough-In6/14/20196/14/20196/14/2019PPASS
DetailsRock A. Hudson
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Entrance, reception, stairway drop lid rough in ok cover
Electrical Rough-In6/10/20196/11/20196/11/2019APASS
DetailsRock A. Hudson
Rough in inspection. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Basement walls and conference hardlid rough in ok cover
Electrical Rough-In5/20/20195/21/20195/21/2019APASS
DetailsRock A. Hudson
UG cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Procedure room underslab and work room rough in ok cover
Electrical Rough-In5/15/20195/16/20195/16/2019APASS
DetailsRock A. Hudson
Wall Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Area (B) walls and hard lids, basement conference room only floor receptacle pour rough in ok cover
Electrical Rough-In3/21/20193/21/20193/21/2019APASS
DetailsRock A. Hudson
Cover inspection. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
West walls only rough in ok cover
Electrical Rough-In3/20/20193/20/20193/20/2019PFAIL
DetailsRock A. Hudson
Danny. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
110.3- Provide documentation on terminating MC with secondary equipment grounding conductor. All have been cut off.
300.4- Where MC is run through holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. All shallow studs west and south sides.