Final | 1/13/2020 | 1/13/2020 | 1/13/2020 | P | CANC |
Rock A. Hudson
|
|
|
ronald Phone #: ###-#### Duplicate request
|
Final | 1/10/2020 | 1/13/2020 | 1/13/2020 | A | PASS |
Rock A. Hudson
|
|
|
Final please. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott Notches cut into duct work to bew patched maintaining access to boxes. Final ok
|
Final | 1/8/2020 | 1/9/2020 | 1/9/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Final please. Have a bless day Phone #: ###-#### Inspection requested via web by Kyle Lott At Building inspectors request need to address work done under ELE16-02769. This permit expired 5-14-19, a new permit shall be pulled covering this work and an inspection must be performed for this work. Called Kyle's number and left information with his receptionist. 110.3- Baseboard manufactureres instructions states receptacles shall not be located above baseboard heaters. 1 in down office. 210.8- GFCI receptacle devices shall be located where readily accessible. In drinking fountains. 314.29- Ceiling boxes shall be located where accessible. HVAC duct covering misc boxes rendering them not accessible.
|
Electrical Rough-In | 11/18/2019 | 11/19/2019 | 11/19/2019 | P | PASS |
Rock A. Hudson
|
|
|
Rough in please. Thank you. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott Basement walls and bathroom hardlid rough in ok cover
|
Electrical Rough-In | 6/12/2019 | 6/13/2019 | 6/13/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Maria Phone #: ###-#### Although moritorium has been lifted to pull building permits the building permit still shall complete plan review and be issued prior to performing work associated with area under building permit. Recall when bulding permit has been issued
|