DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/5/20207/6/20207/6/2020PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by shane miller Corrections made final ok
Rough-In Permanent Service7/1/20207/2/20207/2/2020AFAIL
DetailsJames Ady
Call the above 3 iF NO ANSWER. Phone #: ###-#### Inspection requested via web by shane miller 406.12 Dwelling receps shall be tamper resistant. 406.9A Receps in damp location shall be type WR. 358.42 Couplings and connectors shall be made up tight. 300.9 Interior of raceway above grade in wet location shall be considered a wet location. (Wheather proof recep near A/C romex in conduit, loose connector , Non tamper and non WR,)
Rough-In Permanent Service6/30/20207/1/20207/1/2020ANH
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by shane miller No access reschedule