Final | 7/5/2020 | 7/6/2020 | 7/6/2020 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by shane miller Corrections made final ok
|
Rough-In Permanent Service | 7/1/2020 | 7/2/2020 | 7/2/2020 | A | FAIL |
James Ady
|
|
|
Call the above 3 iF NO ANSWER. Phone #: ###-#### Inspection requested via web by shane miller 406.12 Dwelling receps shall be tamper resistant. 406.9A Receps in damp location shall be type WR. 358.42 Couplings and connectors shall be made up tight. 300.9 Interior of raceway above grade in wet location shall be considered a wet location. (Wheather proof recep near A/C romex in conduit, loose connector , Non tamper and non WR,)
|
Rough-In Permanent Service | 6/30/2020 | 7/1/2020 | 7/1/2020 | A | NH |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by shane miller No access reschedule
|