Permit Information
Permit NumberFIR09-00107
StatusFinaled
Name ALARMCO
Site Address 200 N MAPLE GROVE RD
Project NameMAPLE GROVE BUILDING
Customer Number 
ePlanReview 
Description
12/23/10: PLAN MODIFICATION (5 Initiating devices affected). This plan modification is to provide a new Fire Alarm Control Panel and connect the existing pull station and sprinkler system monitoring devices to it. No duct detectors or HVAC has been indicated. If duct detectors are required and/or provided, a plan modification shall be submitted an approved prior to calling for a final inspection. Also included in this plan modification scope of work is the addition of an IntelliTap module.

2/17/09: This fire alarm permit is to replace the DACT (phone lines) functions with RF Radio for monitoring. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/11/20111/12/20111/12/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/10/20111/11/20111/11/2011PCANC
DetailsTroy Cobbley
Please call Guy at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
INSP-Final Inspection1/7/20111/7/20111/7/2011PCANC
DetailsTroy Cobbley
CARISSA had not corrdinated with Alarmco to perform this inspection. Will need to be rescheduled.
INSP-Final Inspection12/30/20101/3/20111/3/2011AFAIL
DetailsTroy Cobbley
To final this permit both flow switches and both PIV tamper switches need to be tested. The inspector test lines do not have the required orfice mounted therefore a test or these devices could not be completed.
FIR-Aging Inspection10/28/201010/28/201010/28/2010 NR
DetailsTroy Cobbley
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
FIR-Aging Inspection7/7/20107/7/20107/7/2010 NR
DetailsTroy Cobbley
Per Bill the AES inspection scheduling is being addressed.
INSP-Final Inspection4/5/20104/5/20104/5/2010PFAIL
DetailsTroy Cobbley
The AES panel had a Netcon 5. The AES panel was being used as a stand alone facp which is not allowed due to listing. The city approved drawings showed a separate facp connected to the new AES panel. No testing other than the Netcon was performed.
INSP-Final Inspection4/2/20104/5/20104/5/2010AFAIL
DetailsTroy Cobbley
I spoke to Bryan at 7:43 to meet with him first thing. I waited at the project site until 8:15. There was no answer on his phone when I tried to re-contact him. No inspection was performed.
FIR-Aging Inspection5/27/20095/27/20095/27/2009 NR
DetailsTroy Cobbley
work is in progress